App index, Ff transmits fifo data, Is transmits status information – Yokogawa Button Operated MV2000 User Manual

Page 114: Fu transmits the user level

Advertising
background image

4-41

Commands

M-4662

1

2

3

4

5

6

7

App

Index

Description • The most recent measured/computed data

corresponds to the most recent measured/
computed data in the internal memory when
the MV receives the FD command.

• Set the first channel number and last channel

number parameters so that the last channel
number is greater than or equal to the first
channel number.

• Parameters p2 and p3 are valid when p1

is set to 0 or 1. All channels are specified if
parameters p2 and p3 are omitted.

• Set parameters p2 and p3 according to the

table in section 4.3.

FF

Transmits FIFO data

Syntax

FF p1,p2,p3,p4<terminator>
p1

Operation type

GET

Transmit the next block

RESEND

Retransmit the previous output

RESET

Set the most recent data position

(block) to the read position of the
FIFO buffer (block)

p2

First channel number (measurement/

computation/external input channel)

p3

Last channel number (measurement/

computation/external input channel)

p4

Maximum number of blocks that are to be

loaded
1200

RD-MV1004/RD-MV2008/RD-
MV1008

240

RD-MV1006/RD-MV1012/RD-
MV1024/RD-MV2010/RD-MV2020/
RD-MV2030/RD-MV2040/RD-
MV2048

60

Models with the /MC1 external
input channel option

If the measured/computed/external input
data is less than the specified number of
blocks, the MV transmits the available data.

Example

Transmit two blocks of FIFO data from channels
1 to 10.
FFGET,001,010,2

Description • The FIFO buffer is a cyclic buffer, which

overwrites the oldest data. Use the FR
command to set the acquisition period.

• The MV transmits the specified number of

blocks (p4), starting with the block after the
previously read block.

Make sure to read the data within the following

buffer period to prevent data dropouts.
• RD-MV1004
FIFO buffer size: 240 cycles (scan interval)
Maximum buffer period: 240 × (acquisition

interval). Resending is not
possible after the buffer
period elapses.

• Parameters p2 and p4 are valid when p1 is set

to GET.

• If p4 is omitted, the MV transmits all blocks.
• Set the first channel number and last channel

number parameters so that the last channel

number is greater than or equal to the first
channel number.

• For the output flow diagram of FIFO data, see

appendix 5.

• Set parameters p2 and p3 according to the

table in section 4.3.

FL

Transmits a log, alarm summary,

or message summary

Syntax

FL p1,p2<terminator>
p1

Log type

COM

Communication

FTPC

FTP client

ERR

Operation error

LOGIN

Login log

WEB

Web operation

EMAIL

E-mail

SNTP

SNTP access log

DHCP

DHCP access log

ALARM

Alarm summary

MSG

Message summary

MODBUS

Modbus communication log

p2

Maximum read length of the log

1–200

Parameter p1 is COM or
MODBUS

1–1000

Parameter p1 is ALARM

1–450

Parameter p1 is MSG

1–50

Parameter p1 is some type
other than those above

Example

Transmit the 10 most recent operation error logs.
FLERR,10

Description • Transmits the log that is stored in the MV.

• If p2 is omitted, the MV transmits all written

logs.

IS

Transmits status information

Syntax

IS p1<terminator>
p1

Status information output

0

Status information 1 to 4

1

Status information 1 to 8

Example

Transmit status information 1 to 4.
IS0

Description The output status can be masked using the

status filter (IF command). For details on the
status information, see chapter 6.

FU

Transmits the user level

Syntax

FU p1<terminator>
p1

User information output

0

Information about the user
currently logged in

1

Information about the user logged
into a general-purpose service

Example

Transmit information about the user logged into a
general-purpose service.
FU1

4.8 Output Commands (Setting/Measured/Computed Data Output)