Yokogawa Button Operated MV2000 User Manual

Page 161

Advertising
background image

7-8

M-4662

Input Register

Data

Data Type

36001

List of alarms of measurement channels 001 to 004

Bit string

|

|

36012

List of alarms of measurement channels 045 to 048

• Register structure

4ch 3ch 2ch 1ch

Level 3

Level 4

Level 2

Level 1

Indicates the alarm statuses of four channels in a register. Set to 1 when
alarm is activated. The figure above is an example of register 36001
(measurement channels 001 to 004).

36021

List of alarms of computation channels 101 to 104

Bit string

|

|

36035

List of alarms of computation channels 157 to 160

• Register structure: Same as the list of alarms of measurement channels.

36041

List of alarms of external input channels 201 to 204

Bit string

|

|

36100

List of alarms of external input channels 437 to 440

• Register structure: Same as the list of alarms of measurement channels.

• Input registers 36001 to 36100 can be accessed consecutively. All unassigned register bits

are read as zeroes.

Input Register

Data

Data Type

39001

Year

16-bit signed integer

39002

Month

39003

Day

39004

Hour

39005

Minute

39006

Second

39007

Millisecond

39008

(Reserved)

7.3 Modbus Protocol Specifications

Advertising