3 modbus protocol specifications, App index, Modbus client function – Yokogawa Button Operated MV2000 User Manual

Page 156

Advertising
background image

7-3

M-4662

Specifications

1

2

3

4

5

6

7

App

Index

7.3

Modbus Protocol Specifications

Modbus Client Function

Basic Operation

• The MV, operating as a Modbus client device, communicates with Modbus servers

periodically by sending commands at specified intervals.

• This function is independent of the Modbus master function operating over the serial

interface.

• The supported functions are (1) reading data from the input registers and hold

registers on a server and (2) writing data into the hold registers on a server.

Modbus Client Specifications

Communication available via ModbusTCP
Communication media: Ethernet 10Base-T
Read cycle:

Select from the following:

125 ms, 250 ms, 500 ms, 1 s, 2 s, 5 s, and 10 s

Connection retries:

Select the how long to wait before reconnecting after the

connection is dropped due to the expiration of the connection
wait time.

OFF, 10 s, 20 s, 30 s, 1 min, 2 min, 5 min, 10 min, 20 min, 30

min, and 1 h

Connection timeout value: 1 minute

However, if the IP address has not been obtained from the

DHCP server, a communication error results immediately.

Command timeout value: 10 seconds
Server:

Register up to 16 servers

Supported functions: The table below contain functions that the MV supports. To

use the functions, the server device must also support them.

Function Code

Function

Operation

3

Reads the hold register
(4xxxx, 4xxxxx)

The MV reads from the server device hold register
into the communication input channel or external
input channel.

4

Reads the input register
(3xxxx, 3xxxxx)

The MV reads from the server device input register
into the communication input channel or external
input channel.

16

Writes to the hold register
(4xxxx, 4xxxxx)

The MV writes the measured or computed data to
the server device hold register.

Commands

Command type:

R, R-M, W, and W-M

Number of commands: Set up to 16 commands
Data type:

See the table below.

Symbol

Description

INT16

16-bit signed integer

UINT16

16-bit unsigned integer

INT32_B

32-bit signed integer (big endian)

INT32_L

32-bit signed integer (little endian)

UINT32_B

32-bit unsigned integer (big endian)

UINT32_L

32-bit unsigned integer (little endian)

FLOAT_B

32-bit floating point (big endian)

FLOAT_L

32-bit floating point (little endian)

Advertising
This manual is related to the following products: