App index, Tc sets the background color, Tp sets auto group switching – Yokogawa Button Operated MV2000 User Manual

Page 90: Tr sets auto monitor recovery, Tq sets a timer, Tk sets a match timer

Advertising
background image

4-17

Commands

M-4662

1

2

3

4

5

6

7

App

Index

SQ

Sets the LCD brightness and

screen backlight saver

Syntax

SQ p1,p2,p3,p4<terminator>
p1

LCD brightness

1–8

RD-MV1000

1–6

RD-MV2000

p2

Type of display backlight saver function

OFF

Disable the saver function

DIMMER

Dim

TIMEOFF

Turn OFF

p3

Time to switch to saver mode

1MIN

, 2MIN, 5MIN, 10MIN, 30MIN, 1H

p4

Event that causes the MV to return from

saver mode
KEY

Pressing of a key

KEY+ALARM

Pressing of a key or an alarm

occurrence

Query

SQ?

Example

Set the LCD brightness to 2 and the screen
backlight saver function to dim. Set the time to
switch to saver mode to 5 minutes and the event
that causes the MV to return from saver mode to
pressing of a key.
SQ2,DIMMER,5MIN,KEY

Description If p2 is set to OFF, do not specify p3 or p4.

TC

Sets the background color

Syntax

TC p1,p2<terminator>
p1

Display screen (WHITE, BLACK)

p2

Historical trend display (WHITE, CREAM,

LIGHTGRAY, BLACK)

Query

TC?

Example

Set the display background to black and the
historical display background to cream.
TCBLACK,CREAM

TP

Sets auto group switching

Syntax

TP p1<terminator>
p1

Auto scroll time (5S, 10S, 20S, 30S, 1MIN)

Query

TP?

Example

Switch the group at 5-s intervals.
TP5S

TR

Sets auto monitor recovery

Syntax

TR p1<terminator>
p1

Auto recovery time (OFF, 1MIN, 2MIN,

5MIN, 10MIN, 20MIN, 30MIN, 1H)

Query

TR?

Example

Set the auto recovery time to 5 minutes.
TR5MIN

TQ

Sets a timer

If p2 is set to OFF (no timer)

Syntax

TQ p1,p2<terminator>
p1

Timer number (1 to 4)

p2

Timer type (OFF)

If p2 is set to ABSOLUTE (absolute time)

Syntax

TQ p1,p2,p3,p4<terminator>
p1

Timer number (1 to 4)

p2

Timer type (ABSOLUTE)

p3

Time interval (1MIN to 6MIN, 10MIN, 12MIN,

15MIN, 20MIN, 30MIN, 1H to 4H, 6H, 8H,
12H, 24H)

p4

Reference time (hh)

hh

Hour (00 to 23)

If p2 is set to RELATIVE (relative time)

Syntax

TQ p1,p2,p3,p4<terminator>
p1

Timer number (1 to 4)

p2

Timer type (RELATIVE)

p3

Time (hh:mm)

hh

Hour (00 to 24)

mm

Minute (00 to 59)

p4

Reset at computation start (ON/OFF)

Query

TQ[ p1]?

Example

Set the timer number 1 timeout value to 10 hours 30
minutes. Do not reset at start.
TQ1,1,RELATIVE,10:30,OFF

TK

Sets a match timer

If p2 is set to OFF (not use a match timer)

Syntax

TK p1,p2<terminator>
p1

Timer number (1 to 4)

p2

Timer designation (OFF)

If p2 is set to DAY (time designation)

Syntax

TK p1,p2,p3,p4,p5<terminator>
p1

Timer number (1 to 4)

p2

Timer designation (DAY)

p3

Day (1 to 28)

p4

Time (hh:mm) (00:00 to 23:59)

p5

Timer operation (SINGLE, REPEAT)

SINGLE

Single operation

REPEAT

Repetitive operation

If p2 is set to WEEK (day of week/time designation)

Syntax

TK p1,p2,p3,p4,p5<terminator>
p1

Timer number (1 to 4)

p2

Timer designation (WEEK)

p3

Designation of the day of the week (SUN,

MON, TUE, WED, THU, FRI, SAT)

p4

Time (hh:mm) (00:00 to 23:59)

p5

Timer operation (SINGLE, REPEAT)

4.4 Setting Commands (Setting)