Example of a connection to the host device, Four-wire system, Two-wire system – Yokogawa Button Operated MV2000 User Manual

Page 64

Advertising
background image

3-6

M-4662

Example of a Connection to the Host Device

The MV can connect to a host device that has an RS-232, RS422, or RS-485 port.
If the host device has an RS-232 port, use a converter. See the examples below for
typical converter terminals. For details, see the converter manual.

RS-422/485 Port

Converter

SDA(–)

TD(–)

SDB(+)

TD(+)

RDA(–)

RD(–)

RDB(+)

RD(+)

SG

SHIELD

FG

EARTH

There is no problem with connecting a 220-Ω terminator at each end if Omega PLCs or temperature
controllers are also connected in the communication line.

• Four-Wire System

Generally, a four-wire system is used to connect the MV to a host device. In a four-

wire system, the transmission and reception lines need to be crossed over.

Terminator (external) 120 Ω 1/2W or greater

#1

Do not connect terminators to #1 through #n-1.

RS-422/485

terminal on the MV

#2

#n

(#n 32)

Terminator (external)

Host device

side

SG

RDB( + )

RDA( - )

SDB( + )

SDA( - )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

• Two-Wire System

Connect the transmission signals to the reception signals with the same polarity on the

RS422/485 terminal block. Only two wires are used to connect to the external device.

Terminator (external) 120 Ω 1/2W or greater

#1

Do not connect terminators to #1 through #n-1.

RS-422/485

terminal on the MV

#2

#n

(#n 31)

Terminator (external)

Host device

SG

RDB( + )

RDA( - )

SDB( + )

SDA( - )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(B)

(A)

(B)

(A)

FG

SG

RD B

RD A

SD B

SD A

(SG)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(B)

(A)

3.2 Connecting the MV