West Control Solutions Pro-EC44 User Manual

Page 126

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 119

26

NI120 RTD

28

0 to 20mA DC

29

4 to 20mA DC

30

0 to 50mV DC

31

10 to 50mV DC

32

0 to 5V DC

33

1 to 5V DC

34

0 to 10V DC

35

2 to 10V DC

36

Potentiometer

Input 2 Engineering Units

Value

Engineering Units For Display

Dec

1101

17485 34970

RW

0

= None

Hex

044D

444D

889A

1

= °C (Default for Europe)

2

= °F (Default for USA)

3

= °K

4

= Bar

5

= pH

6

= %

7

= %RH

8

= PSI

Input 2 Maximum Display Decimal
Places

Value

Maximum Number Of Decimal Places In Display

Dec

1102

17486 34972

RW

0

None (e.g. 1234)

Hex

044E

444E

889C

1

One (e.g. 123.4)

2

Two (e.g. 12.34)

3

Three (e.g. 1.234)

Input 2 Scaled Input Lower Limit

Scaling Value Low Limit

Dec

1103

17487 34974

RW

Valid between input 2 range maximum and minimum (see

Specifications section for input details)

Hex

044F

444F

889E

Input 2 Scaled Input Upper Limit

Scaling Value High Limit

Dec

1104

17488 34976

RW

Valid between input 2 range maximum and minimum (see

Specifications section for input details)

Hex

0450

4450

88A0

Input 2 Process Variable Offset

Single Point Calibration PV Offset

Dec

1105

17489 34978

RW

Used for Single Point Calibration of input 2

Valid between the scaled input lower & upper limits

Hex

0451

4451

88A2

Input 2 Filter Time Constant

Input 2 Process Input Filter Time

Dec

1106

17490 34980

RW

Valid between 0.0 and 512.0

Hex

0452

4452

88A4

Input 2 Process Variable

Process Input 2 Value

Dec

1107

17491 34982

RO

The current input 2 process value

Hex

0453

4453

88A6

Input 2 Signal /Sensor Break Flag

Value

Process Input Break Status

Dec

1108

17492 34984

RO

0

Inactive

Hex

0454

4454

88A8

1

Active (break detected)

Input 2 Signal Under Range Flag

Value

Process Input Under Range Status

Dec

1109

17493 34986

RO

0

Inactive

Hex

0455

4455

88AA

1

Active (under-range detected)

Advertising