6 Messages & Error Indications

Plug-in Module Problems

If an invalid or unknown module is detected in one of the plug-in module slots during the
power-up self-test, the message

Fault Found, Press R, for details” is shown. This is

followed by

Replace faulty module in Module Slot n, Press R,” (where n is the faulty slot

location). The Service Contact information is displayed next showing details of who to
contact if a fault persists

Replace the module in slot “n”. If this does not solve the problem, return the instrument for
investigation.

CAUTION:

Do not continue using the product until the the error is resolved.

Sensor Break Detection

Whenever a problem is detected with a process variable or auxiliary input connection, the
displayed value for that input

is replaced with the word “OPEN”; except in Ratio control

where an open input 1 or 2 is shown as “x1-Open” or “x2-Open”. See Redundant Input
(page 83) to protect critical processes from sensor faults.

This may be the result of a failed sensor, a broken connection or an input circuit fault.
In this condition, the control outputs go to the pre-set power value (see Control Configuration
– page 50).

CAUTION:

Correct the signal/wiring problem to continue normal operation.

Un-Calibrated Input Detection

The instrument is fully calibrated during manufacture. If a fault occurs and calibration data is
lost, the process input displays are

replaced with the word “ERROR” and error is shown

instead of “Calibrated” for effected inputs in Service & Product Information mode.
In this condition, the control outputs go to the pre-set power value (see Control Configuration
– page 50).

CAUTION:

Perform a full base calibration of the input before continuing

normal operation (see page 72). If the problem persists, return the
instrument for servicing.

PV Over-range or Under-range Indication

If a measured process input value is more than 5% above than the Scaled Input Upper Limit,
its value is replace by the word “HIGH” to indicate that it is out of range.

If a measured process input value is more than 5% below than the Scaled Input Lower Limit,
its value is replaced

by the word “LOW” to indicate that it is out of range.