Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 168

Alarm 5 Input Source

Value

Source

Dec

6207

22591 45182

RW

0

Input 1

Hex

183F

583F

B07E

1

Input 2

2

Aux A Input

3

Control Loop 1 Primary Power

4

Control Loop 1 Secondary Power

5

Control Loop 2 Primary Power

6

Control Loop 2 Secondary Power

7

Loop 1

8

Loop 2

Alarm 5 Type

Value

Alarm 5 Type

Dec

6208

22592 45184

RW

0

Unused

Hex

1840

5840

B080

1

Process High Alarm

2

Process Low Alarm

3

Deviation Alarm (SP-PV)

4

Band Alarm

5

Input Rate of Change

6

Input/Sensor Break Alarm

7

Loop Alarm

10

% memory used

11

High Power Alarm

12

Low Power Alarm

Alarm 5 Value

Value At Which Alarm 5 Activates

Dec

6209

22593 45186

RW

Limited by input scaling for alarm types 1 to 4.

Not used for alarms 5, 6 or 7.

0 to 100% for alarms 10 to 12.

Hex

1841

5841

B082

Alarm 5 Rate of Change Value

Process Variable Rate of Change Alarm Threshold

Dec

6214

22598 45196

RW

Value for Rate of Change Alarm. Alarm 5 activates when PV

change exceeds this level. From 0.0 to 99999

Hex

1846

5846

B08C

Alarm 5 Hysteresis

Alarm 5 Hysteresis Value

Dec

6210

22594 45188

RW

Deadband value (on

“safe” side of alarm), through which signal

must pass before Alarm 5 deactivates.

Limited by the input scaling span

Hex

1842

5842

B084

Alarm 5 Inhibit Enable/disable

Value

Alarm 5 Power-up/Setpoint Change Inhibit

Dec

6211

22595 45190

RW

0

Disabled

Hex

1843

5843

B086

1

Enabled

Alarm 5 Status

Value

Alarm 5 Status

Dec

6212

22596 45192

RO

0

Inactive

Hex

1844

5844

B088

1

Active

Alarm 5 Inhibit Status

Value

Alarm 5 Inhibit Status

Dec

6213

22597 45194

RO

0

Not Inhibited

Hex

1845

5845

B08A

1

Inhibited

Alarm 5 Label

Main Language Name For Alarm 5 In Status Screen

Dec

6215

22599 45198

RW

8 ASCII characters replacing the title "Alarm 5" in alarm status

screens when main display language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.