Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 249

Output Specifications

Output Module Types

Plug-in Slot 1:

Single SPDT Relay, Single SSR Driver, Triac or DC linear.

Plug-in Slot 2:

Single SPDT Relay, Dual SPST Relay, Single SSR Driver, Dual SSR
Driver, Triac or 24VDC Transmitter Power Supply.

Plug-in Slot 3:

Single SPDT Relay, Dual SPST Relay, Single SSR Driver, Dual SSR
Driver, Triac or 24VDC Transmitter Power Supply.

Base Option 4 & 5:

Slot 4 SPDT Relay (std.). Slot 5 SPDT Relay (optional.)

Base Option 6 & 7:

Slots 6 & 7 DC Linear (optional.)

Single Relay Output 1-3 Performance

Positions

Optional in Plug-in Modules 1, 2 & 3.

Contact Type:

Single pole double throw (SPDT).

Contact Rating:

2A resistive at 120/240V AC

Lifetime:

>500,000 operations at full rated AC voltage/current. De-rate if
switching DC loads.

Isolation:

Reinforced safety isolation from inputs and other outputs.

CAUTION:

Plastic pegs prevent fitting of older non-reinforced single relay

modules

Remove the peg to fit dual relays (all dual relay modules have

reinforced isolation).

Dual Relay Output 2-3 Performance

Positions

Optional in Plug-in Modules 2 & 3.

Contact Type:

2 x Single pole single throw (SPST) relays with shared common.

Contact Rating:

2A resistive at 120/240V AC.

Lifetime:

>200,000 operations at full rated AC voltage/current. De-rate if
switching DC loads.

Isolation:

Reinforced safety isolation from inputs and other outputs.

Base Relay 4-5 Output Performance

Positions

Base outputs 4 & 5.

Contact Type:

1 x Single pole single throw (SPST).

Contact Rating:

2A resistive at 120/240V AC.

Lifetime:

>200,000 operations and which contacts at full rated voltage/current.
De-rate if switching DC loads.

Isolation:

Reinforced safety isolation from inputs and other outputs.