23 specifications, Reference test conditions, Universal process inputs – West Control Solutions Pro-EC44 User Manual

Page 252: General input 1 and 2 specifications, Thermocouple input, Thermocouple types & ranges, Specifications

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 245

23 Specifications

Reference Test Conditions

Ambient Temperature:

20

C ±2

C.

Relative Humidity:

60 to 70%.

Supply Voltage:

100 to 240V AC 50Hz ±1%.

Source Resistance:

<10Ω for thermocouple input.

RTD Lead Resistance:

<0.1Ω/lead balanced (Pt100).

Universal Process Inputs

General Input 1 and 2 Specifications

Input Sample Rate:

100mS (Ten samples per second)

Input Filter Time

0.0 (OFF), 0.1 to 100.0 seconds in 0.1 second increments.

Input Resolution:

16 bits. Always four times better than the display resolution.

Supply Voltage:

Negligible effect on readings within the specified supply tolerances.

Humidity Influence:

Negligible effect on readings if non-condensing.

Temp. Stability:

Error <0.01% of span per °C change in ambient temperature.

Input Impedance:

V DC:

47KΩ.

mA DC:

5Ω.

Other ranges:

Greater than 10M

resistive.

Isolation:

Reinforced safety isolation from outputs and other inputs.

User Calibration:

Single or two point. +ve values are added -ve subtracted from PV.

PV Display:

Displays process variable up to 5% over and 5% under span.

Thermocouple Input

Thermocouple Types & Ranges

Sensor
Type

Range in

C

Range in

F

Sensor

Type

Range in

C

Range in

F

B

+100 to 1824°C +211 to 3315°F

L

0 to 762°C

32 to 1402°F

C

0 to 2320°C

32 to 4208°F

N

0 to 1399°C

32 to 2551°F

D

0 to 2315°C

32 to 4199°F

PtRh20%:
PtRh40%

0 to 1850°C

32 to 3362°F

E

-240 to 1000°C

-400 to 1832°F

R

0 to 1759°C

32 to 3198°F

J (default) -200 to 1200°C

-328 to 2192°F

S

0 to 1762°C

32 to 3204°F

K

-240 to 1373°C

-400 to 2503°F

T

-240 to 400°C

-400 to 752°F

Note: Defaults to °F for USA units. Defaults to °C for non-USA units.
The Scaled Input Upper Limit and Scaled Input Lower Limit parameters, can be
used to restrict range. An optional decimal place can be displayed.