Loop 2 Pre-Tune Set

Value

PID Set Pre-tune Will Optimize

Dec

4497

20881 41762

RW

0

PID Set 1

Hex

1191

5191

A322

1

PID Set 2

2

PID Set 3

3

PID Set 4

4

PID Set 5

Loop 2 Pre-Tune Engage/disengage

Value

Pre-Tune Engage/disengage For Loop 2

Dec

4425

20809 41618

RW

0

Pre-Tune OFF

Hex

1149

5149

A292

1

Run Pre-Tune

Loop 2 Self-Tune Engage/disengage

Value

Self-Tune Engage/disengage For Loop 2

Dec

4426

20810 41620

RW

0

Self-Tune OFF

Hex

114A

514A

A294

1

Self-Tune ON

Loop 2 Loop Alarm Type

Value

Loop Alarm Type For Loop 2

Dec

4427

20811 41622

RW

1

User Defined Time

Hex

114B

514B

A296

2

Automatic (2x Integral Time)

Loop Alarm Time

Loop Alarm Activation Time

Dec

4428

20812 41624

RW

1 to 5999 Seconds after output loop 2 power reaches saturation

Hex

114C

514C

A298

Loop 2 Primary Power

Loop 2 Primary Power Level

Dec

4429

20813 41626

RO

The current loop 2 primary power level (0 to 100%)

Hex

114D

514D

A29A

Loop 2 Secondary Power

Loop 2 Secondary Power Level

Dec

4430

20814 41628

RO

The current loop 2 secondary power level (0 to 100%)

Hex

114E

514E

A29C

Loop 2 Combined Power

Loop 2 Combined Primary & Secondary Power Level

Dec

4431

20815 41630

RO

The current loop 2 combined PID power level (-100 to 100%)

Hex

114F

514F

A29E

Loop 2 Pre-Tune Status

Value

Pre-Tune Status For Loop 2

Dec

4432

20816 41632

RO

0

Inactive

Hex

1150

5150

A2A0

1

Active

Loop 2 Self-Tune Status

Value

Self-Tune Status For Loop 2

Dec

4433

20817 41634

RO

0

Inactive

Hex

1151

5151

A2A2

1

Active

Loop 2 Loop Alarm status

Value

Loop Alarm Status For Loop 2

Dec

4434

20818 41636

RO

0

Inactive

Hex

1152

5152

A2A4

1

Active

Loop 2 Input Failure Pre-set Power

Loop 2 Input Sensor Break Pre-set Power

Dec

4435

20819 41638

RW

The pre-defined power output applied if input signal is lost

0 to 100% (-100% to 100% for dual control).

Hex

1153

5153

A2A6

Loop 2 Auto Pre-tune

Value

Auto Pre-Tune At Every Power-up For Loop 2

Dec

4436

20820 41640

RW

0

Disabled

Hex

1154

5154

A2A8

1

Enabled