West Control Solutions Pro-EC44 User Manual

Page 171

Advertising
background image

Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 164

Alarm 1 Main Label

Main Language Name For Alarm 1 In Status Screen

Dec

6151

22535 45070

RW

8 ASCII characters replacing the title "Alarm 1" in alarm status

screens when main display language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1807

5807

B00E

Alarm 1 Alternate Label

Alternate Language Name For Alarm 1 In Status Screen

Dec

6152

22536 45072

RW

8 ASCII characters replacing the title "Alarm 1" in alarm status

screens when the alternate language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1808

5808

B010

Alarm 1 Minimum Duration

Alarm 1 Minimum Duration

Dec

6153

22537 45074

RW

Minimum time alarm 1 must be passed its threshold before

activating (deactivation is not affected by this parameter).

From 0 to 9999 secs

Hex

1809

5809

B012

Alarm 2 Input Source

Value

Source

Dec

6159

22543 45086

RW

0

Input 1

Hex

180F

580F

B01E

1

Input 2

2

Aux A Input

3

Control Loop 1 Primary Power

4

Control Loop 1 Secondary Power

5

Control Loop 2 Primary Power

6

Control Loop 2 Secondary Power

7

Loop 1

8

Loop 2

Alarm 2 Type

Value

Alarm 2 Type

Dec

6160

22544 45088

RW

0

Unused

Hex

1810

5810

B020

1

Process High Alarm

2

Process Low Alarm

3

Deviation Alarm (SP-PV)

4

Band Alarm

5

Input Rate of Change

6

Input/Sensor Break Alarm

7

Loop Alarm

10

% memory used

11

High Power Alarm

12

Low Power Alarm

Alarm 2 Value

Value At Which Alarm 2 Activates

Dec

6161

22545 45090

RW

Limited by input scaling for alarm types 1 to 4.

Not used for alarms 5, 6 or 7.

0 to 100% for alarms 10 to 12.

Hex

1811

5811

B022

Alarm 2 Rate of Change Value

Process Variable Rate of Change Alarm Threshold

Dec

6166

22550 45100

RW

Value for Rate of Change Alarm. Alarm 2 activates when PV

change exceeds this level. From 0.0 to 99999

Hex

1816

5816

B02C

Alarm 2 Hysteresis

Alarm 2 Hysteresis Value

Dec

6162

22546 45092

RW

Deadband value (on

“safe” side of alarm), through which signal

must pass before Alarm 2 deactivates.

Limited by the input scaling span

Hex

1812

5812

B024

Alarm 2 Inhibit Enable/disable

Value

Alarm 2 Power-up/Setpoint Change Inhibit

Dec

6163

22547 45094

RW

0

Disabled

Hex

1813

5813

B026

1

Enabled