Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 170

Alarm 6 Inhibit Status

Value

Alarm 6 Inhibit Status

Dec

6229

22613 45226

RO

0

Not Inhibited

Hex

1855

5855

B0AA

1

Inhibited

Alarm 6 Label

Main Language Name For Alarm 6 In Status Screen

Dec

6231

22615 45230

RW

8 ASCII characters replacing the title "Alarm 6" in alarm status

screens when main display language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1857

5857

B0AE

Alarm 6 Alternate Label

Alternate Language Name For Alarm 6 In Status Screen

Dec

6232

22616 45232

RW

8 ASCII characters replacing the title "Alarm 6" in alarm status

screens when the alternate language is used, read/written with

Modbus functions 16 or 23. Valid characters are 0 to 9, a to z, A

to Z, plus Я ц ( ) - and _.

Hex

1858

5858

B0B0

Alarm 6 Minimum Duration

Alarm 6 Minimum Duration

Dec

6233

22617 45234

RW

Minimum time alarm 6 must be passed its threshold before

activating (deactivation is not affected by this parameter).

From 0 to 9999 secs

Hex

1859

5859

B0B2

Alarm 7 Input Source

Value

Source

Dec

6239

22623 45246

RW

0

Input 1

Hex

185F

585F

B0BE

1

Input 2

2

Aux A Input

3

Control Loop 1 Primary Power

4

Control Loop 1 Secondary Power

5

Control Loop 2 Primary Power

6

Control Loop 2 Secondary Power

7

Loop 1

8

Loop 2

Alarm 7 Type

Value

Alarm 7 Type

Dec

6240

22624 45248

RW

0

Unused

Hex

1860

5860

B0C0

1

Process High Alarm

2

Process Low Alarm

3

Deviation Alarm (SP-PV)

4

Band Alarm

5

Input Rate of Change

6

Input/Sensor Break Alarm

7

Loop Alarm

10

% memory used

11

High Power Alarm

12

Low Power Alarm

Alarm 7 Value

Value At Which Alarm 7 Activates

Dec

6241

22625 45250

RW

Limited by input scaling for alarm types 1 to 4.

Not used for alarms 5, 6 or 7.

0 to 100% for alarms 10 to 12.

Hex

1861

5861

B0C2

Alarm 7 Rate of Change Value

Process Variable Rate of Change Alarm Threshold

Dec

6246

22630 45260

RW

Value for Rate of Change Alarm. Alarm 7 activates when PV

change exceeds this level. From 0.0 to 99999

Hex

1866

5866

B0CC

Alarm 7 Hysteresis

Alarm 7 Hysteresis Value

Dec

6242

22626 45252

RW

Deadband value (on “safe” side of alarm), through which signal

must pass before Alarm 7 deactivates.

Limited by the input scaling span

Hex

1862

5862

B0C4