Page 189

Instruction Sequence to read a profile

1. Use the command RP to read the profile header data

2. Use the command RS to read the 1

st

segment’s data

3. Use the command RS to read the 2

nd

segment’s data.

4. Repeat steps 2 and 3 until an end segment is reached.

The following rules apply when creating a profile over communications:

Profiles must always be terminated with an end segment.

Segments cannot be added after an end segment has been added.

All changes made to the selected profile are immediately saved in the instrument.

Creating or Editing a Profile Header

Creating Or Editing A Profile Header - Request (to instrument)

Field Name

Data

Comments

Dec

Hex

Unit Address

A/R

A/R

The network address ID of the instrument.

Function Code

23

17

Requires the multi read/write function.

Read Start Address High Byte

32

20

Read Start Address Low Byte

6

6

Read Quantity Of Registers High Byte

0

0

Read Quantity Of Registers Low Byte

1

1

Write Start Address High Byte

32

20

Write Start Address Low Byte

6

6

Write Quantity Of Registers High Byte

0

0

Write Quantity Of Registers Low Byte

20 or 21

14 or 15

20dec / 0x14hex if creating a profile at the
next available location.
21dec / 0x15hex if creating a profile at a
specified location, or editing a profile.

Byte Count

40 or 42

28 or 2A

40dec / 0x28hex if creating a profile at the
next available location.
42dec / 0x2Ahex if creating a profile at a
specified location, or editing a profile.

Command Code High Byte

67, 69 or

87

43, 45 or

57

0x43hex (67dec) if creating a profile at the
next available location.
45hex (69 dec) / 57hex (87dec) if creating a
profile at a specified location, or editing a
profile.

Command Code Low Byte

80

50

Profile Number High Byte

A/R

A/R

Note: The profile number is not included
in the message when creating a profile
at the next available position.

Profile Number Low Byte

A/R

A/R