Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 158

Loop 2 Control Action

Value

Direction Of Control Action

Dec

4411

20795 41590

RW

0

Direct Acting

Hex

113B

513B

A276

1

Reverse Acting

PID Set 1 - Primary Prop Band

PID Set 1 Primary Proportional Band For Loop 2

Dec

4412

20796 41592

RW

Primary Proportional Band for Gain Set 1.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

113C

513C

A278

PID Set 1 - Secondary Prop Band

PID Set 1 Secondary Proportional Band For Loop 2

Dec

4413

20797 41594

RW

Secondary Proportional Band for Gain Set 1.

1 display unit to 9999 units,

but limited to 10 x scaled input span. 0 = On-Off control

Hex

113D

513D

A27A

PID Set 1 - Integral Time

PID Set 1 Integral Time For Loop 2

Dec

4414

20798 41596

RW

Gain Set 1 integral time constant for loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

113E

513E

A27C

PID Set 1 - Derivative Time

PID Set 1 Derivative Time For Loop 2

Dec

4415

20799 41598

RW

Gain Set 1 derivative time constant for loop 2

0.1 to 5999 Seconds. 0 or 6000 = OFF

Hex

113F

513F

A27E

Loop 2 Manual Reset (Bias)

PID Set 1 Manual Reset (Bias) For Loop 2

Dec

4416

20800 41600

RW

Working point from 0 to 100 for single control or

-100 to 100 for dual control (primary & secondary)

Hex

1140

5140

A280

PID Set 1 - Overlap/Deadband

PID Set 1 - Overlap or Deadband For Loop 2

Dec

4417

20801 41602

RW

PID Set 1 overlap (+ve) or deadband (-ve) between primary &

secondary prop bands. In display units - limited to 20% of the

combined band width.

Hex

1141

5141

A282

PID Set 1 - On/Off Differential

PID Set 1 - On/Off Control Differential For Loop 2

Dec

4420

20804 41608

RW

The on-off control hysteresis (deadband) for PID Set 1.

1 to 300 display units, centred about the setpoint.

Hex

1144

5144

A288

Loop 2 Primary Power Upper limit

Loop 2 Primary Power Upper limit

Dec

4421

20805 41610

RW

10 to 100%

but must be at least 10% above the primary power lower limit.

Hex

1145

5145

A28A

Loop 2 Primary Power Lower Limit

Loop 2 Primary Power Lower Limit

Dec

4422

20806 41612

RW

0 to 90%

but must be at least 10% below the primary power upper limit.

Hex

1146

5146

A28C

Loop 2 Secondary Upper Power limit

Loop 2 Secondary Upper Power limit

Dec

4423

20807 41614

RW

10 to 100%

but must be at least 10% above the secondary power lower limit.

Hex

1147

5147

A28E

Loop 2 Secondary Power Lower limit

Loop 2 Secondary Power Lower limit

Dec

4424

20808 41616

RW

0 to 90%

but must be at least 10% below the primary power upper limit.

Hex

1148

5148

A290

Loop 2 Pre-Tune Method

Value

Pre-Tune type

Dec

4496

20880 41760

RW

0

Standard

Hex

1190

5190

A320

1

Pre-tune at Value

Loop 2 Pre-Tune at Value

Value To Pre-Tune Loop 2

Dec

4499

20883 41766

RW

Valid between the scaled input lower & upper limits

(applies if Pre-Tune Type = Pre-Tune at Value)

Hex

1193

5193

A326