Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 74

6. If the input is misconnected or an incorrect signal is applied, the calibration will be aborted

and the values will not be altered. The display will show “Failed: Signal Too Small!” or
“Failed: Signal Too Large!”. Correct the problem and repeat that phase before continuing.

7. Press

R

to select the next calibration phase.

8. Repeat this process for each input type until all the phases are calibrated. For each phase,

ensure that the correct input is applied, using the appropriate connections.

9. If the instrument has 2 process inputs, when the first input sequence completes, the Input

2 Calibration Status screen is displayed. Repeat the procedure from 3 above for this input.

10. Once calibration is complete, recorder versions will ask for a Calibration Reminder Date.

If required, this can be changed to the date of your next calibration check. Ensure that
Calibration Reminders are enabled in Input Configuration to receive a reminder.

11. Press

R

+

U

to exit to the main menu.

Note: The Calibration Mode automatically exits if there is no button activity for
two minutes.