Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 120

Input 2 Signal Over Range Flag

Value

Process Input Over Range Status

Dec

1110

17494 34988

RO

0

Inactive

Hex

0456

4456

88AC

1

Active (over-range detected)

Input 2 Cold Junction Compensation

Value

CJC Status

Dec

1111

17495 34990

RW

0

Disabled

Hex

0457

4457

88AE

1

Enabled (default)

Input 2 Multi-point Scaling Enable

Value

Multi-point Scaling Status

Dec

1129

17513 35026

RW

0

Disabled

Hex

0469

4469

88D2

1

Enabled (only if the input type is linear)

Input 2 Scale Point 1

Multi-Point Scaling Point 1

Dec

1130

17514 35028

RW

Percentage of the scaled input where multi-point scaling value 1

is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

046A

446A

88D4

Input 2 Display Point 1

Multi-Point Scaling Display Value For Point 1

Dec

1131

17515 35030

RW

Value to display at multi-point scaling point 1

Valid between the scaled input lower & upper limits

Hex

046B

446B

88D6

Input 2 Scale Point 2

Multi-Point Scaling Point 2

Dec

1132

17516 35032

RW

Percentage of the scaled input where multi-point scaling value 2

is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

046C

446C

88D8

Input 2 Display Point 2

Multi-Point Scaling Display Value For Point 2

Dec

1133

17517 35034

RW

Value to display at multi-point scaling point 2

Valid between the scaled input lower & upper limits

Hex

046D

446D

88DA

Input 2 Scale Point 3

Multi-Point Scaling Point 3

Dec

1134

17518 35036

RW

Percentage of the scaled input where multi-point scaling value 3

is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

046E

446E

88DC

Input 2 Display Point 3

Multi-Point Scaling Display Value For Point 3

Dec

1135

17519 35038

RW

Value to display at multi-point scaling point 3

Valid between the scaled input lower & upper limits

Hex

046F

446F

88DE

Input 2 Scale Point 4

Multi-Point Scaling Point 4

Dec

1136

17520 35040

RW

Percentage of the scaled input where multi-point scaling value 4

is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

0470

4470

88E0

Input 2 Display Point 4

Multi-Point Scaling Display Value For Point 4

Dec

1137

17521 35042

RW

Value to display at multi-point scaling point 4

Valid between the scaled input lower & upper limits

Hex

0471

4471

88E2

Input 2 Scale Point 5

Multi-Point Scaling Point 5

Dec

1138

17522 35044

RW

Percentage of the scaled input where multi-point scaling value 5

is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

0472

4472

88E4

Input 2 Display Point 5

Multi-Point Scaling Display Value For Point 5

Dec

1139

17523 35046

RW

Value to display at multi-point scaling point 5

Valid between the scaled input lower & upper limits

Hex

0473

4473

88E6

Input 2 Scale Point 6

Multi-Point Scaling Point 6

Dec

1140

17524 35048

RW

Percentage of the scaled input where multi-point scaling value 6

is applied.

0.1 to 100.0% *set to 100% ends scaling sequence at that point.

Hex

0474

4474

88E8

Input 2 Display Point 6

Multi-Point Scaling Display Value For Point 6

Dec

1141

17525 35050

RW

Value to display at multi-point scaling point 6

Valid between the scaled input lower & upper limits

Hex

0475

4475

88EA