Pro-EC44 2-Loop Graphical Profile Controller & Recorder

Pro-EC44 Product Manual - 59540-1 October 2013

Page 51

Set n

– Integral

The integral time value (Automatic Reset) for PID Set n (n = up to 5).
Adjustable from 1s to 99min 59s or OFF

Only the set(s) in use shown.

Set n

– Derivative

The derivative time value (Rate) for PID Set n (n = up to 5). Adjustable
from 1s to 99 min 59s or OFF

Only the set(s) in use are shown.

Set n

– Overlap

The overlap (+ve) or deadband (-ve) between primary & secondary
proportional bands for PID Set n (n = up to 5). In display units - limited to
20% of the combined primary & secondary prop band width.

Set n

– On/Off Diff

The on-off control hysteresis (deadband) for PID Set n (n = up to 5).
Adjustable from 1 to 300 display units, centred about the setpoint

Only

the set(s) in use are shown.

Set n - Breakpoint

The SP or PV value where the PID Set n (n = up to 5) if gain scheduling is
used. Set 1 is used from Scaled Input Lower Limit to the Set 2 Breakpoint,
then Set 2 used to the Set 3 Breakpoint etc. If a breakpoint is set to OFF
subsequent PID sets are not used. The final PID set runs to the Scaled
Input Upper Limit.

Manual Reset (Bias)

The Manual Reset value to bias the control working point within the
proportional band(s). Adjustable from 0 to 100% for single control or 100 to
+100% for dual control. Typically set to 80% of typical power needed for
setpoint, but lower values can help inhibit start-up overshoot.

Anti Wind-Up Limit

Adjusts the value at which the “reset wind-up inhibit” is applied. Above this
power level further integral action is suspended. Adjustable from 10 to
100% of PID power. Lower values inhibit overshoot.

Caution:

If set too low control deviation can occur (the process

settles, but is offset above or below the setpoint). It this is observed,
increase the value until the deviation error is removed.

Ratio SFAC

The nominal ratio scaling factor used for Stoichiometric Ratio Control in
burner fuel/air control applications. Adjustable from 0.010 to 99.999.
– refer to the Ratio Control section on page 81Error! Bookmark not
defined.

Ratio NO

A constant between 0.0 & 9999.0, added to the x1 (input 1) value in
Stoichiometric Ratio Control mode to allow for atomizing air when
calculating the process value. The total air flow is therefore x1 + NO.

Primary Cycle Time

The primary power cycle time. Adjustable from 0.5 to 512 seconds. Applied
for time proportioned primary relay, SSR driver or triac control outputs

Not used for VMD Control modes.

Secondary Cycle
Time

The secondary power cycle time when dual control is used. Adjustable
from 0.5 to 512 seconds. Applied for time proportioned primary relay, SSR
driver or triac control outputs

Not used for VMD Control modes.

Primary Power Lower
Limit

The minimum primary output power limit. The control algorithm will not
allow the power output fall below this level. Adjustable from 0 to 90% but is
always at least 10% below the primary power upper limit.

Caution:

The instrument will not be able to control the process

correctly if the lower limit is above the level required to maintain
setpoint.

Primary Power Upper
Limit

The maximum primary output power limit. The control algorithm will not
allow the power output rise above this level. Adjustable from 10 to 100%
but is always at least 10% above the primary power lower limit.

Caution:

The instrument will not be able to control the process

correctly if the upper limit is below the level required to maintain
setpoint.