Preinstallation requirements, Table and backboard, Network interface – AT&T System 25 User Manual

Page 40

Advertising
background image

INSTALLATION

PREINSTALLATION REQUIREMENTS

The AT&T System 25 Reference Manual (555-540-200)

provides a complete

listing of System 25 equipment location requirements. Before installation

begins, check the items described in this section.

Caution:

System 25 cross connect hardware must be located in a

restricted access area only.

Table and Backboard

Verify that an equipment table and cross-connect backboard are installed.
(See Figure 2-8 for a sample layout.) The cross-connect backboard is a 48-

inch by 96-inch by

3/4-inch plywood panel, mounted horizontally 30-inches

above the floor and within 5 feet of the location chosen for the cabinets.

If wall space in the equipment room is limited, an alternate layout may be
provided. If more than four 617A Panels are required, this alternate layout

will require more than one 48-inch by 96-inch plywood panel. See Install

Equipment Room Station Cabling

for details.

Network Interface

The RJ21X network interface (CO lines) installed by the telephone company

must be located within 25 feet of the system cabinets. In addition to the
RJ21X network interface, an RJ2GX interface is required for tie

lines. For T1

interfaces, RJ48X network interfaces must be provided.

If System 25 is

replacing another system and no additional lines are required, the network
interfaces used with the previous system should already be in place.

The network interfaces should also include a coupled bonding conductor
extended from the building service entrance.

2-16

Advertising