Line compensation/equalization, Connect coupled bonding conductor (cbc), Figure 2-25 – AT&T System 25 User Manual

Page 82: Csu connections

Advertising
background image

INSTALLATION

Connect the CSU

The CSU can be powered by the line or from a locally provided -48 V dc

power supply. Figure 2-25 shows the connections for connecting the CSU.

The 48 V and GRD leads are optional according to how the CSU is powered.

H 6 0 0 3 0 7 , 0 2

C O N N E C T O R

CABLE (NOTE)

NOTE : FOR DISTANCES OVER 50 FEET ( 15.2 M)

USE C6E CONNECTOR CABLE(S) BETWEEN
H600 307,02 CONNECTOR CABLE AND DS1
TRUNK CIRCUIT PACK .

T O L O C A L L Y

P R O V I D E D - 4 8 V

P O W E R S U P P L Y

Figure 2-25.

CSU Connections

Line Compensation/Equalization

Determine the cable distance of the line, either to the line termination or
“phantom” midpoint of a direct connection.

Refer to the System 25

Administration Manual (555-540-650) for instructions on setting the line
e q u a l i z a t i o n .

Connect Coupled Bonding Conductor (CBC)

Each network interface (RJ48X) is associated with a service entrance

(protector block) ground. A CBC should be connected to this ground. If the

local telephone company has not run a CBC up to the network interface, you

should run it yourself. Use #12, #14, or #16 AWG wire. Start the CBC at
the protector block ground, and run it as close as possible to the facilities
cable. If possible, tie wrap the CBC to the facilities cable. Do not use spare
pairs in the telephone company cable for this purpose.

2-58

Advertising