Secondary protection, Figure 2-9, Ac power distribution—multiple cabinet system – AT&T System 25 User Manual

Page 45

Advertising
background image

INSTALLATION

Secondary Protection

External secondary protection, located at the trunk access area of the
System 25 cross-connect field, is required for all trunks and off-premises
lines. Refer to Table 2-B for approved trunk protectors.

FROM AC
LOAD CENTER

(TWO SEPARATELY

FUSED 15 AMP
C I R C U I T S )

SINGLE
POINT
GROUND

H

GROUND

I

LOAD
CENTER

II

(GREEN)

(#14 AWG)

TO CABINET NO. 1

GROUND BAR MOUNTED ‘

GROUND BLOCK (MAX.

ON 4“ BOX (SQUARE D

LENGTH = 2 0 F T . )

PK9GTA OR APPROVED

EQUIVALENT)

4“ BOX (RACO 230
OR EQUIVALENT)

HUBBELL RECPTS.

( 5262 15 AMP

OR EQUIVALENT)

4“ COVER (RACO 807
OR EQUIVALENT)

APPROVED
BUILDING GROUND

(#6 AWG, COPPER)

Figure 2-9.

AC Power Distribution—Multiple Cabinet System

2-21