Compressor Rotation

PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal

injury.

CAUTION

!

On 3--phase units with scroll compressors, it is important

to be certain compressor is rotating in the proper

direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect service gauges to suction and discharge pres-

sure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start--up.

NOTE: If the suction pressure does not drop and the
discharge pressure does not rise to normal levels:

4. Note that the evaporator fan is probably also rotating

in the wrong direction.

5. Turn off power to the unit.
6. Reverse any two of the unit power leads.
7. Reapply power to the compressor.

The suction and discharge pressure levels should now

move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong

direction, the unit makes an elevated level of noise and
does not provide cooling.

Filter Drier

Replace whenever refrigerant system is exposed to

atmosphere. Only use factory specified liquid--line filter

driers with working pressures no less than 650 psig. Do

not install a suction--line filter drier in liquid line. A

liquid--line filter drier designed for use with Puron

refrigerant is required on every unit.

Outdoor Fan Location

See Fig. 21.

1. Shut off unit power supply. Install lockout tag.
2. Remove condenser--fan assembly (grille, motor, and

fan).

3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 21.
5. Tighten setscrews to 84 in--lbs (9.5 Nm).
6. Replace condenser--fan assembly.

Conduit

0.14 in + 0.0 / -0.03

C08448

Fig. 21 -- Outdoor Fan Adjustment

Troubleshooting Cooling System

Refer to Table 6 for additional troubleshooting topics.