Caution – Bryant 548J User Manual

Page 31

Advertising
background image

31

Table 13 – Detector Indicators

CONTROL OR INDICATOR

DESCRIPTION

Magnetic test/reset switch

Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in

the normal state.

Alarm LED

Indicates the sensor is in the alarm state.

Trouble LED

Indicates the sensor is in the trouble state.

Dirty LED

Indicates the amount of environmental compensation used by the sensor

(flashing continuously = 100%)

Power LED

Indicates the sensor is energized.

Detector Cleaning

Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is

flashing continuously or sooner if conditions warrant.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
If the smoke detector is connected to a fire alarm

system, first notify the proper authorities that the

detector is undergoing maintenance then disable the

relevant circuit to avoid generating a false alarm.

CAUTION

!

1. Disconnect power from the duct detector then remove

the sensor’s cover. (See Fig. 44.)

2. Using a vacuum cleaner, clean compressed air, or a

soft bristle brush, remove loose dirt and debris from

inside the sensor housing and cover.

Use isopropyl alcohol and a lint--free cloth to remove

dirt and other contaminants from the gasket on the

sensor’s cover.

3. Squeeze the retainer clips on both sides of the optic

housing then lift the housing away from the printed

circuit board.

4. Gently remove dirt and debris from around the optic

plate and inside the optic housing.

5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a

sensor alarm test.

Airflow

HVAC duct

Sampling

tube

Retainer
clip

Optic
plate

Optic
housing

Sensor
housing

C07305

Fig. 44 -- Sensor Cleaning Diagram

Indicators

Normal State
The smoke detector operates in the normal state in the

absence of any trouble conditions and when its sensing

chamber is free of smoke. In the normal state, the Power

LED on both the sensor and the controller are on and all

other LEDs are off.
Alarm State
The smoke detector enters the alarm state when the

amount of smoke particulate in the sensor’s sensing

chamber exceeds the alarm threshold value. (See

Table 13.) Upon entering the alarm state:

S

The sensor’s Alarm LED and the controller’s Alarm

LED turn on.

S

The contacts on the controller’s two auxiliary relays

switch positions.

S

The contacts on the controller’s alarm initiation relay

close.

S

The controller’s remote alarm LED output is activated

(turned on).

S

The controller’s high impedance multiple fan shutdown

control line is pulled to ground Trouble state.

The SuperDuct duct smoke detector enters the trouble

state under the following conditions:

S

A sensor’s cover is removed and 20 minutes pass before

it is properly secured.

S

A sensor’s environmental compensation limit is reached

(100% dirty).

S

A wiring fault between a sensor and the controller is

detected.

An internal sensor fault is detected upon entering the

trouble state:

S

The contacts on the controller’s supervisory relay

switch positions. (See Fig. 45.)

S

If a sensor trouble, the sensor’s Trouble LED and the

controller’s Trouble LED turn on.

S

If 100% dirty, the sensor’s Dirty LED turns on and the

controller’s Trouble LED flashes continuously.

S

If a wiring fault between a sensor and the controller, the

controller’s Trouble LED turns on but not the sensor’s.

548J

Advertising