Legend and Notes for Table 50

LEGEND:

CO

--- Convenient outlet

DISC

--- Disconnect

FLA

--- Full load amps

IFM

--- Indoor fan motor

LRA

--- Locked rotor amps

MCA

--- Minimum circuit amps

MOCP

--- Maximum over current protection

PE

--- Power exhaust

UNPWR CO

--- Unpowered convenient outlet

NOTES:

1. In compliance with NEC requirements for multimotor and

combination load equipment (refer to NEC Articles 430 and

440), the overcurrent protective device for the unit shall be

fuse or HACR breaker. Canadian units may be fuse or circuit

breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply

voltage is greater than 2%. Use the following formula to de-

termine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.

APPENDIX V. WIRING DIAGRAM LIST

Wiring Diagrams

548J***A

SIZE

VOLTAGE

CONTROL

POWER

04A

208/230---1---60

48TM501434.02

48TM501435.02

208/230---3---60

48TM501434.02

48TM501436.02

460---3---60

48TM501434.02

48TM501436.02

575---3---60

48TM501434.02

48TM501436.02

05A

208/230---1---60

48TM501434.02

48TM501435.02

208/230---3---60

48TM501434.02

48TM501436.02

460---3---60

48TM501434.02

48TM501436.02

575---3---60

48TM501434.02

48TM501436.02

06A

208/230---1---60

48TM501434.02

48TM501435.02

208/230---3---60

48TM501434.02

48TM501436.02

460---3---60

48TM501434.02

48TM501436.02

575---3---60

48TM501434.02

48TM501436.02

07A

208/230---3---60

48TM501434.02

48TM501436.0

460---3---60

48TM501434.02

48TM501436.0

575---3---60

48TM501434.02

48TM501436.0

All

RTU---MP*

48TM501531.03
548J***D

SIZE

VOLTAGE

CONTROL

POWER

08D

208/230---3---60

48TM501370.03

48TM501371.04

460---3---60

48TM501370.03

48TM501371.04

575---3---60

48TM501370.03

48TM501371.04

09D

208/230---3---60

48TM501370.03

48TM501371.04

460---3---60

48TM501370.03

48TM501371.04

575---3---60

48TM501370.03

48TM501371.04

All

RTU---MP*

48TM501448.03

NOTE: Component arrangement on Control; Legend on Power Schematic
* The RTU--MP control label overlays a portion of the base unit control label. The base unit label drawing and the control option drawing are required to

provide a complete unit control diagram.