Table 17 – Troubleshooting Alarms

POINT NAME

BACnet

OBJECT

NAME

ACTION TAKEN BY

CONTROL

RESET

METHOD

PROBABLE CAUSE

Safety Chain Alarm

safety_chain

Alarm Generated

Immediate Shutdown

Automatic

Over load Indoor Fan or Electric Heater overheat.

Fire Shutdown Alarm

fire_alarm

Alarm Generated

Immediate Shutdown

Automatic

Smoke detected by smoke detector or

configuration incorrect

Space Temp Sensor

Failure

spt_alarm

Alarm Generated

Immediate Shutdown

Automatic

Faulty, shorted, or open thermistor caused by

wiring error or loose connection.

SAT Sensor Alarm

sat_alarm

Alarm Generated

Immediate Shutdown

Automatic

Faulty, shorted, or open thermistor caused by

wiring error or loose connection.

High Space Temp Alarm

spt_hi

Alarm Generated

Automatic

The space temperature has risen above the cool

setpoint by more than the desired amount.

Low Space Temp Alarm

spt_lo

Alarm Generated

Automatic

The space temperature has dropped below the

heat setpoint by more than the desired amount.

High Supply Air Temp

sat_hi

Alarm Generated

Automatic

SAT is greater then 160 degrees for more than 5

minutes.

Low Supply Air Temp

sat_lo

Alarm Generated

Automatic

The supply air temperature is below 35_F for

more than 5 minutes.

Supply Fan Failed to

Start

sf_fail

Alarm Generated

Immediately

disable Operation

Automatic

Tripped Circuit Breaker, Broken belt, Bad indoor

fan motor, Configuration incorrect, Bad fan status

switch.

Supply Fan in Hand

sf_hand

Alarm Generated

Ramp down Operations

Automatic

Bad Fan Status Switch, Configuration incorrect.

Compressor Safety

Alarm

dx_compstat

Alarm Generated

Automatic

Compressor would not start.

Setpoint Slider Alarm

slide_alarm

Alarm Generated Offset

set to zero

Automatic

STO sensor is open or shorted for more then 5

seconds.

Dirty Filter Alarm

filter

Alarm Generated

Automatic/

reset timer

when

configured

with or

without

switch

Dirty Filter, supply fan run time exceeded, filter

switch configuration wrong.

Switch Configuration

Alarm

sw_cfg_alarm

Alarm Generated

Disable misconfigured

switch functions

Configure

correctly

More than one binary input is configured for the

same purpose. More then one discrete input is

configured to provide the same function.

Misconfigured Analog

Input

an_cfg_alarm

Alarm Generated

Disable 4 selectable

analog inputs

Configure

correctly

More then one analog input is configured to

provide the same function.

OAT Sensor Alarm

oat_alarm

Alarm Generated

Economizer and Low

ambient DX cooling

lockout disabled.

Automatic

Faulty, shorted, or open thermistor caused by

wiring error or loose connection.

Space RH Sensor Alarm

sprh_alarm

Alarm Generated

Dehumidification

disabled

Automatic

Sensor reading is out of range. Bad sensor, bad

wiring, or sensor configured incorrectly.

Outdoor RH Sensor

Alarm

oarh_alarm

Alarm Generated

Automatic

Sensor reading is out of range. Bad sensor, bad

wiring, or sensor configured incorrectly.

High Space Humidity

sprh_hi

Alarm Generated

Automatic

IRH is greater then 70% for more then 10

minutes.

Low Space Humidity

sprh_lo

Alarm Generated

Automatic

IRH is less then 35% for more then 10 minutes.

IAQ Sensor Alarm

iaq_alarm

Alarm Generated

Disables IAQ Operation

Economizer moves to

minimum position

Automatic

Sensor reading is out of range. Bad sensor, bad

wiring, or sensor configured incorrectly.

OAQ Sensor Alarm

oaq_alarm

Alarm Generated

Set OAQ to 400

Automatic

Sensor reading is out of range. Bad sensor, bad

wiring, or sensor configured incorrectly.

High Carbon Dioxide

Level

co2_hi

Alarm Generated

Automatic

CO2 reading is above 1200ppm.

Supply Fan Runtime

Alarm

sf_rntm

Alarm Generated

clear the

timer

Supply fan run time exceeded user defined limit.

Compressor 1 Runtime

Alarm

dx1_rntm

Alarm Generated

clear the

timer

Compressor run time limit is exceeded.

Compressor 2 Runtime

Alarm

dx2_rntm

Alarm Generated

clear the

timer

Compressor run time limit is exceeded.