Bryant 548J User Manual

Page 52

Advertising
background image

52

TR1

24 Vac

COM

TR

24

Vac

HOT

1

2

3

4

5

EF

EF1

+

_

P1

T1

P

T

N

EXH

2V

10V

EXH

Set

Set

2V

10V

2V

10V

DCV

DCV

Free

Cool

B

C

A

D

SO+

SR+

SR

SO

AQ1

AQ

DCV

Min

Pos

Open

Max

N1

C06038

Fig. 77 -- EconoMi$er IV Control

Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV

controller uses two enthalpy sensors (HH57AC078 and

CRENTDIF004A00), one in the outside air and one in the

return air duct. The EconoMi$er IV controller compares

the outdoor air enthalpy to the return air enthalpy to

determine EconoMi$er IV use. The controller selects the

lower enthalpy air (return or outdoor) for cooling. For

example, when the outdoor air has a lower enthalpy than

the return air, the EconoMi$er IV opens to bring in

outdoor air for free cooling.
Replace the standard outside air dry bulb temperature

sensor with the accessory enthalpy sensor in the same

mounting location. (See Fig. 66.) Mount the return air

enthalpy sensor in the return air duct. (See Fig. 75.)

Wiring is provided in the EconoMi$er IV wiring harness.

(See Fig. 66.) The outdoor enthalpy changeover setpoint is

set with the outdoor enthalpy setpoint potentiometer on

the EconoMi$er IV controller. When using this mode of

changeover

control,

turn

the

enthalpy

setpoint

potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation

control based on the level of CO

2

measured in the space

or return air duct.
Mount the accessory IAQ sensor according to

manufacturer specifications. The IAQ sensor should be

wired to the AQ and AQ1 terminals of the controller.

Adjust the DCV potentiometers to correspond to the DCV

voltage output of the indoor air quality sensor at the

user-determined setpoint. (See Fig. 78.)

0

1000

2000

3000

4000

5000

6000

2

3

4

5

6

7

8

800 ppm
900 ppm
1000 ppm
1100 ppm

RANGE

CONFIGURA

TION

(ppm)

DAMPER VOLTAGE FOR MAX VENTILATION RATE

CO SENSOR MAX RANGE SETTING

2

C06039

Fig. 78 -- CO

2

Sensor Maximum Range Settings

If a separate field-supplied transformer is used to power

the IAQ sensor, the sensor must not be grounded or the

EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper

position represents the minimum ventilation position for

VOC

(volatile

organic

compounds)

ventilation

requirements. The maximum demand ventilation position

is used for fully occupied ventilation.
When demand ventilation control is not being used, the

minimum position potentiometer should be used to set the

occupied ventilation position. The maximum demand

ventilation position should be turned fully clockwise.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan

runs based on damper position (if accessory power

exhaust is installed). The setpoint is modified with the

Exhaust Fan Setpoint (EXH SET) potentiometer. (See

Fig. 72.) The setpoint represents the damper position

above which the exhaust fans will be turned on. When

there is a call for exhaust, the EconoMi$er IV controller

provides a 45 ±15 second delay before exhaust fan

activation to allow the dampers to open. This delay allows

the damper to reach the appropriate position to avoid

unnecessary fan overload.
Minimum Position Control
There is a minimum damper position potentiometer on the

EconoMi$er IV controller. (See Fig. 72.) The minimum

damper position maintains the minimum airflow into the

building during the occupied period.
When using demand ventilation, the minimum damper

position represents the minimum ventilation position for

VOC

(volatile

organic

compound)

ventilation

requirements. The maximum demand ventilation position

is used for fully occupied ventilation.
When demand ventilation control is not being used, the

minimum position potentiometer should be used to set the

occupied ventilation position. The maximum demand

ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the

minimum amount of outdoor air, as required by local

codes, to enter the building. Make minimum position

adjustments with at least 10_F temperature difference

between the outdoor and return-air temperatures.

548J

Advertising