Bryant 548J User Manual

Page 64

Advertising
background image

64

de--energized as the dampers close below the PE--On

setpoint.

Damper movement from full closed to full open (or vice

versa) will take between 1

1

/

2

and 2

1

/

2

minutes.

Heating With EconoMi$er IV

During Occupied mode operation, indoor fan operation

will be accompanied by economizer dampers moving to

Minimum Position setpoint for ventilation. If indoor fan is

off, dampers will close. During Unoccupied mode

operation, dampers will remain closed unless a DCV

demand is received.

When the room temperature calls for heat (W1 closes), the

heating controls are energized as described in Heating,

Unit Without Economizer above.

Defrost Cycle

During the Heating Mode, frost and ice can develop on

the outdoor coil. Defrost sequence will clear the frost and

ice from the coil by briefly reversing the Heating

sequence periodically.

A window to test for a need to run the Defrost cycle opens

30 minutes after the end of the last Defrost cycle or the

previous test window closed. If DFT2 is closed, the

Defrost cycle will start. Output at OF is removed; outdoor

fans stop during the Defrost cycle. Output P3--6 (RVS2) is

energized; reversing valve solenoid RVS2 is energized and

reversing valve 2 changes position, placing Circuit 2 in a

Cooling mode flow, directing hot gas into the outdoor coil

where its heat melts the frost and looses the ice on the coil

face.

During the Defrost cycle, output EHEAT is also energized

(if not already energized by a thermostat W2 demand);

electric heaters will be energized.

During the Defrost Cycle, LED1 on the DFB will be

illuminated.

The Defrost cycle ends when DFT2 opens (as liquid

temperature exiting the coil rises above DFT2 setpoint) or

the defrost cycle runs for 10 minutes. Output at EHEAT is

removed; electric heaters will be de--energized (unless

thermostat has a W2 demand). Output at OF is restored;

outdoor fans start again. Output at P3--6 (RVS2) is

removed; reversing valve 2 returns to Heating position.

During the Circuit 2 defrost cycle, Circuit 1 may also

enter defrost cycle if DFT1 closes. When DFT1 closes,

DFB output P3--7 (RVS1) is energized; reversing valve

solenoid 1 is energized, causing reversing valve 1 to

switch position and place Circuit 1 in a Cooling mode

flow. Defrost in Circuit 1 ends when DFT1 opens or

defrost cycle in Circuit 2 is terminated.

Defrost cycle is fixed at a maximum 10 minute duration
limit. The period to test and initiate a Defrost cycle can be
selected at 30, 60, 90 or 120 minutes.

Emergency Heat

Emergency Heat is a non--staged heating cycle that uses

the unit’s electric heaters only (no compression heating is

energized). Emergency Heat is initiated when the defrost

board receives an input signal at W2 (P2--6) but there is

no input signal at W1 (P2--7). This signal combination can

be provided by thermostat configuration, manual external

switch selection or by servicer disconnecting the W1 field

connection.

Upon initiation of the Emergency Heat sequence, the DFB

will issue output signals at IFO (P3--9) and EHEAT; IFM

will run and electric heaters will be energized.

When space heating load is satisfied, the input signal at

W2 (P2--6) will be removed. Output at EHEAT is

removed; electric heaters are de--energized. After the Fan

Delay period, the signal at IFO (P3--9) is removed; IFM

stops.

Demand Controlled Ventilation

If a field--installed sensor is connected to the EconoMi$er

IV control, a Demand Controlled Ventilation strategy will

operate automatically. As the level in the space increases

above the setpoint (on the EconoMi$er IV controller), the

minimum position of the dampers will be increased

proportionally, until the Maximum Ventilation setting is

reached. As the space level decreases because of the

increase in fresh air, the outdoor--damper will follow the

higher demand condition from the DCV mode or from the

free--cooling mode.

DCV operation is available in Occupied and Unoccupied

periods with EconoMi$er IV. However, a control

modification will be required on the 50TC unit to

implement the Unoccupied period function.

Supplemental Controls

Compressor Lockout Relay (CLO) – The CLO is available
as a factory-installed option or as a field-installed
accessory. Each compressor has a CLO. The CLO
compares the demand for compressor operation (via a
24-v input from Y at CLO terminal 2) to operation of the
compressor (determined via compressor current signal
input at the CLO’s current transformer loop); if the
compressor current signal is lost while the demand input
still exists, the CLO will trip open and prevent the
compressor from restarting until the CLO has been
manually reset. In the lockout condition, 24-v will be
available at terminal X. Reset is accomplished by
removing the input signal at terminal 2; open the
thermostat briefly or cycle the main power to the unit.

Phase Monitor Relay (PMR) – The PMR protects the unit
in the event of a loss of a phase or a reversal of power line
phase in the three-phase unit power supply. In normal
operation, the relay K1 is energized (contact set closed)
and red LED indicator is on steady. If the PMR detects a
loss of a phase or a phase sequence reversal, the relay K1
is energized, its contact set is opened and unit operation is
stopped; red LED indicator will blink during lockout
condition. Reset of the PMR is automatic when all phases

548J

Advertising