Bryant 548J User Manual

Page 23

Advertising
background image

23

Auxiliary (Electric) Heat control — The 548J unit can be

equipped with one or two auxiliary electric heaters, to

provide a second stage of Heating. The DFB will energize

this Heating system for a Stage 2 Heating command

(heaters operate concurrently with both compressors in the

Stage 2 Heating cycle), for an Emergency Heating

sequence (compressors are off and only the electric

heaters are energized) and also during the Defrost cycle

(to eliminate a “cold blow” condition in the space).

Defrost — The defrost control mode is a time/temperature

sequence. There are two time components: The

continuous run period and the test/defrost cycle period.

The temperature component is provided by the defrost

thermostat(s) (DFT1 and DFT2 (08--09 only) mounted on

the outdoor coil.

The continuous run period is a fixed time period between

the end of the last defrost cycle (or start of the current

Heating cycle) during which no defrost will be permitted.

This period can be set at 30, 60, 90 or 120 minutes by

changing the positions of DIP switches SW1 and SW2

(see Fig. 28 and Table 10). The default run periods are 30

minutes for unit sizes 04--07 and 90 minutes for unit sizes

08--09.

C09283

Fig. 28 -- DIP Switch Settings — Defrost Board

At the end of the continuous run period, the defrost

control will test for a need to defrost. On unit sizes 04--07

(single compressor designs), DFT1 controls the start and

termination of the defrost cycle. If DFT1 is still open, the

defrost test/run window is closed and the control repeats

the continuous run period. If DFT1 is closed, the defrost

cycle is initiated. The defrost period will end when DFT1

opens (indicating the outdoor coil has been cleared of

frost and ice) or a 10 minute elapsed period expires,

whichever comes first.

On unit sizes 08 and 09 (two circuit designs), DFT2

(located on the bottom circuit of the outdoor coil) controls

the start and termination of the defrost cycle. If DFT2 is

still open, the defrost test/run window is closed and the

control repeats the continuous run period. If DFT2 is

closed, the defrost cycle is initiated in Circuit 2. The

defrost period will end when DFT2 opens (indicating the

outdoor coil has been cleared of frost and ice) or a 10

minute elapsed period expires, whichever comes first.

On sizes 08--09, Circuit 1’s defrost thermostat DFT1

(located on the upper circuit of the outdoor coil) cannot

initiate a unit defrost cycle; only DFT2 may do this. But

once Circuit 2 is in defrost, the DFB will monitor the

status of DFT1. If DFT1 closes during a Circuit 2 defrost

cycle, Circuit 1 will also enter a defrost cycle. Circuit 1’s

defrost cycle will end when DFT1 opens (indicating the

upper portion of the outdoor coil is cleared of frost and

ice) or the Circuit 2 defrost cycle is terminated.

At the end of the unit defrost cycle, the unit will be

returned to Heating cycle for a full continuous run period.

If the space heating load is satisfied and compressor

operation is terminated, the defrost control will remember

where the run period was interrupted. On restart in

Heating, the defrost control will resume unit operation at

the point in the run period where it was last operating.

Defrost Thermostats — These are temperature switches

that monitor the surface temperature of the outdoor coil

circuits. These switches are mounted on the liquid tube

exiting the outdoor coil heating circuits. These switches

close on temperature drop at 30_F (--1_C) and reset open

on temperature rise at 80_F (27_C).

Indoor Fan Off Delay — The DFB can provide a 30 sec

delay on Indoor Fan Off if the thermostat’s fan selector

switch is set on AUTO control. DIP Switch SW3 on the

DFB selects use of the fan off time delay feature. Setting

SW3 in the OPEN position turns the Fan Off Delay

feature on; setting SW3 in the CLOSED position disables

this feature. The delay period begins when Y1 demand or

W1 demand by the space thermostat is removed.

Defrost Speedup Functions — The DFB permits the

servicer to speed--up the defrost cycle. There are two

speed--up sequences: relative speed--up and an immediate

forced defrost. Speed--up sequences are initiated by

shorting jumper wires JMP17 and JMP18 together (see

Fig. 26); use a straight--edge screwdriver.

Shorting the jumpers for a period of 1 to 3 secs reduces

the defrost timer periods by a factor of 0.1 sec/minute.

(For example, the 90 min run period is reduced to 9 secs.)

The DFB will step the unit through a Heating cycle and a

Defrost cycle using these reduced time periods. This mode

ends after the Defrost cycle.

Table 10 – Dip Switch Position

Switch No.

1

2

1

2

1

2

1

2

3

1

1

J

1

J

1

J

J

1

On

0

J

J

0

J

0

J

0

0

J

Off

90 minutes

60 minutes

30 minutes

120 minutes

Fan Delay

548J

Advertising