if the GFCI receptacle does not trip as required. Press the

RESET button to clear the tripped condition.

CO8283

UNIT

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER

TERMINALS

208,

230

240

L1: RED +YEL

L2: BLU + GRA

H1 + H3

H2 + H4

460

480

L1: RED

Splice BLU + YEL

L2: GRA

H1

H2 + H3

H4

575

600

L1: RED

L2: GRA

H1

H2

Fig. 24 -- Powered Convenience Outlet Wiring

Maintenance: Periodically test the GFCI receptacle by

pressing the TEST button on the face of the receptacle.

This should cause the internal circuit of the receptacle to

trip and open the receptacle. Check for proper grounding

wires and power line phasing if the GFCI receptacle does

not trip as required. Press the RESET button to clear the

tripped condition.

Fuse on powered type: The factory fuse is a Bussman

“Fusetron” T--15, non--renewable screw--in (Edison base)

type plug fuse.

Using unit--mounted convenience outlets: Units with

unit--mounted convenience outlet circuits will often

require that two disconnects be opened to de--energize all

power to the unit. Treat all units as electrically energized

until the convenience outlet power is also checked and

de--energization is confirmed. Observe National Electrical

Code Article 210, Branch Circuits, for use of convenience

outlets.

HEAT PUMP CONTROLS

Controls Terminal Board

The Controls Terminal Board (CTB) is a large printed

circuit board that is located in the center of the unit

control box. This printed circuit board contains multiple

termination strips and connectors to simplify factory

control box wiring and field control connections.

Terminals are clearly marked on the board surface. See

Fig 25.

The CTB contains no software and no logic. But it does

include seven configuration jumpers that are cut to

configure the board to read external optional and

accessory controls, including that the unit is a heat pump.

C09274

Fig. 25 -- Controls Terminal Board (CTB)

Table 7 – Jumper Configuration

Jumper

Control Function

Note

JMP1

Phase Monitor

JMP2

Occupancy Control

JMP3

Smoke Detector Shutdown

JMP4

Remote Shutdown

JMP5

Heat Pump / Reheat

548J default: Cut

JMP6

Heat Pump / Reheat

548J default: Cut

JMP7

Heat Pump / Reheat

548J default: Cut

Jumpers JMP5, JMP6 and JMP7 are located in notches

across the top of the CTB (see Fig. 25 ). These jumpers

are factory cut on all heat pump units. Visually check

these jumpers to confirm that they have been cut.

PROTECTIVE CONTROLS

Compressor Protection

Overcurrent
The compressor has internal linebreak motor protection.

548J