5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to

operation. No troubleshooting or testing is done by

performing the following procedure.

1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to

previous setting.

4. Set minimum position, DCV setpoint, and exhaust

potentiometers to previous settings.

5. Remove 620--ohm resistor from terminals SR and +.

6. Remove 1.2 kilo--ohm checkout resistor from

terminals SO and +. If used, reconnect sensor from

terminals SO and +.

7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo--ohm resistor from T and T1.

Reconnect wires at T and T1.

10. Remove jumper from P to P1. Reconnect device at P

and P1.

11. Apply power (24 vac) to terminals TR and TR1.

WIRING DIAGRAMS

See Fig. 79 and Fig. 80 for typical wiring diagrams.

C09199

Fig. 79 -- 548J Typical Unit Wiring Diagram -- Power (08D, 208/230--3--60)

548J