Rtu--mp troubleshooting – Bryant 548J User Manual

Page 42

Advertising
background image

42

C07170

Fig. 64 -- BACview

6

Handheld Connections

RTU--MP Troubleshooting

Communication LEDs
The LEDs on the RTU--MP (see Fig. 46) indicate if the

controller is speaking to the devices on the network. The

LEDs should reflect communication traffic based on the

baud rate set. The higher the baud rate the more solid the

LEDs will appear. See Table 16 for further information.

Table 16 – RTU--MP LEDs

The LEDs on the RTU---MP show the status of certain functions

If this LED is on...

Status is...

Power

The RTU MP has power

Rx

The RTU MP is receiving data from the network segment

Tx

The RTU MP is transmitting data over the network segment

DO#

The digital output is active

The

Run and Error LEDs indicate control module and network status

If Run LED shows...

And Error LED shows...

Status is...

2 flashes per second

Off

Normal

2 flashes per second

2 flashes,

alternating with

Run LED

Five minute auto---restart delay after

system error

2 flashes per second

3 flashes,

then off

Control module has just been

formatted

2 flashes per second

4 flashes,

then pause

Two or more devices on this network

have the same ARC156 network address

2 flashes per second

On

Exec halted after frequent system errors

or control programs halted

5 flashes per second

On

Exec start---up aborted, Boot is running

5 flashes per second

Off

Firmware transfer in progress, Boot is

running

7 flashes per second

7 flashes per second, alternating with

Run LED

Ten second recovery period after

brownout

14 flashes per second

14 flashes per second,

alternating with Run LED

Brownout

On

On

Failure. Try the following solutions:
S

Turn the RTU---MP off, then on.

S

Format the RTU---MP.

S

Download memory to the RTU---MP.

S

Replace the RTU---MP.