HEAT PUMP REFRIGERATION

SYSTEM

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal

injury, death and/or equipment damage.
This system uses Puron

R

refrigerant which has

higher pressures than R--22 and other refrigerants. No

other refrigerant may be used in this system. Gauge

set, hoses, and recovery system must be designed to

handle Puron refrigerant. If unsure about equipment,

consult the equipment manufacturer.

!

WARNING

Outdoor Coil

The 548J outdoor coil is fabricated with round tube

copper hairpins and plate fins of various materials and/or

coatings (see “Appendix I -- Model Number Significance”

to identify the materials provided in this unit). All unit

sizes use composite--type two--row coils. Composite

two--row coils are two single--row coils fabricated with a

single return bend end tubesheet.

Indoor Coil

The indoor coil is traditional round--tube, plate--fin

technology. Tube and fin construction is of various

optional materials and coatings (see Model Number

Format). Coils are multiple--row.

Outdoor Coil Maintenance and Cleaning

Recommendation

Routine cleaning of coil surfaces is essential to maintain

proper operation of the unit. Elimination of contamination

and removal of harmful residues will greatly increase the

life of the coil and extend the life of the unit. The

following maintenance and cleaning procedures are

recommended as part of the routine maintenance activities

to extend the life of the coil.
Remove Surface Loaded Fibers
Surface loaded fibers or dirt should be removed with a

vacuum cleaner. If a vacuum cleaner is not available, a

soft non--metallic bristle brush may be used. In either

case, the tool should be applied in the direction of the fins.

Coil surfaces can be easily damaged (fin edges can be

easily bent over and damage the coating of a protected

coil) if the tool is applied across the fins.

NOTE: Use of a water stream, such as a garden hose,

against a surface loaded coil will drive the fibers and dirt
into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Periodic Clean Water Rinse
A periodic clean water rinse is very beneficial for coils

that are applied in coastal or industrial environments.

However, it is very important that the water rinse is made

with very low velocity water stream to avoid damaging

the fin edges. Monthly cleaning as described below is

recommended.

PERSONAL INJURY AND UNIT DAMAGE

HAZARD
Failure to follow this caution may result in personal

injury or equipment damage.
Only approved cleaning is recommended.

CAUTION

!

Routine Cleaning of Indoor Coil Surfaces
Periodic cleaning with Totaline

®

environmentally sound

coil cleaner is essential to extend the life of coils. This

cleaner is available from our Replacement Components

Division as part number P902--0301 for one gallon

container, and part number P902--0305 for a 5 gallon

container. It is recommended that all coils, including

standard

aluminum,

pre--coated,

copper/copper or

E--coated

coils

be

cleaned

with

the

Totaline

environmentally sound coil cleaner as described below.

Coil cleaning should be part of the unit’s regularly

scheduled maintenance procedures to ensure long life of

the coil. Failure to clean the coils may result in reduced

durability in the environment.

Avoid the use of

S

coil brighteners

S

acid cleaning prior to painting

S

high pressure washers

S

poor quality water for cleaning

Totaline

environmentally

sound

coil

cleaner

is

nonflammable, hypoallergenic, non bacterial, and a

USDA accepted biodegradable agent that will not harm

the coil or surrounding components such as electrical

wiring, painted metal surfaces, or insulation. Use of

non--recommended coil cleaners is strongly discouraged

since coil and unit durability could be affected.

Clean coil as follows:

1. Turn off unit power, tag disconnect.
2. Remove top panel screws on outdoor coil end of unit.
3. Remove coil corner post. See Fig. 11. To hold top

panel open, place coil corner post between top panel

and center post. See Fig. 12.

548J