Bryant 548J User Manual

Page 60

Advertising
background image

60

service test. Indoor fans and outdoor fans are controlled

normally to maintain proper unit operation. All normal

cooling alarms and alerts are functional.
NOTE: Circuit A is always operated with Circuit B due
to outdoor fan control on Circuit A. Always test Circuit A
first, and leave it on to test other Circuits.
The Heating submenu is used to change output status for

the individual heat stages, gas or electric. The fans and

cooling service test outputs are reset to OFF for the

heating service test. All normal heating alarms and alerts

are functional.

Configuration

The RTU--MP controller configuration points affect the

unit operation and/or control. Review and understand the

meaning and purpose of each configuration point before

changing it from the factory default value. The submenus

containing configuration points are as follows: Unit,

Cooling, Heating, Inputs, Economizer, IAQ, Clock--Set,

and User Password (USERPW). Each configuration point

is described below under its according submenu.
Unit
Start Delay
This refers to the time delay the unit will wait after power

up before it pursues any specific operation.

Factory Default = 5 sec

Range = 0--600 sec

Filter Service Hours
This refers to the timer set for the Dirty Filter Alarm.

After the number of runtime hours set on this point is

exceeded the corresponding alarm will be generated, and

must be manually cleared on the alarm reset screen after

the maintenance has been completed. The timer will then

begin counting its runtime again for the next maintenance

interval.

Factory Default = 600 hr

NOTE: Setting this configuration timer to 0, disables the
alarm.
Supply Fan Service Hours
This refers to the timer set for the Supply Fan Runtime

Alarm. After the number of runtime hours set on this point

is exceeded the corresponding alarm will be generated,

and must be manually cleared on the alarm reset screen

after the maintenance has been completed. The timer will

then begin counting its runtime again for the next

maintenance interval.

Factory Default = 0 hr

NOTE: Setting this configuration timer to 0, disables the
alarm.
Compressor1 Service Hours
This refers to the timer set for the Compressor 1 Runtime

Alarm. After the number of runtime hours set on this point

is exceeded the corresponding alarm will be generated,

and must be manually cleared on the alarm reset screen

after the maintenance has been completed. The timer will

then begin counting its runtime again for the next

maintenance interval.

Factory Default = 0 hr

NOTE: Setting this configuration timer to 0, disables the

alarm.
Compressor2 Service Hours
This refers to the timer set for the Compressor 2 Runtime

Alarm. After the number of hours set on this point is

exceeded the corresponding alarm will be generated, and

must be manually cleared on the alarm rest screen after

the maintenance has been completed. The timer will then

begin counting its runtime again for the next maintenance

interval

Factory Default = 0 hr

NOTE: Setting this configuration timer to 0, disables the
alarm.
Cooling
Number of Compressor Stages
This refers to the number of mechanical cooling stages

available on a specific unit. Set this point to “One Stage”

if there is one compressor in the specific unit, set to “Two

Stage” if there are two compressors in the unit, and set to

“None” if economizer cooling ONLY is desired.

Factory Default = One Stage for 1 compressor units

Two Stage for 2 compressor units

Cooling/Econ SAT Low Setpt
The supply air temperature must remain above this value

to allow cooling with the economizer and/or compressors.

There is 5_F plus and minus deadband to this point. If the

SAT falls below this value during cooling, all compressors

will be staged off. The economizer will start to ramp

down to minimum position when the SAT = this

configuration +5_F.

Factory Default = 50_F

Range = 45--75_F

Cooling Lockout Temp
This defines the minimum outdoor air temperature that

cooling mode can be enabled and run. If the OAT falls

below this threshold during cooling, then compressor

cooling will not be allowed.

Factory Default = 45_F

Range = 0--65_F

Heating
Heating SAT High Setpt
The supply air temperature must remain below this value

to allow heating. There is 5_F plus and minus deadband to

this point. If the SAT rises above this value during heating

the heat stages will begin to decrease until the SAT has

dropped below this value.

Factory Default = 120_F

Range = 95--150_F

Heating Lockout Temp
This defines the maximum outdoor air temperature that

heating mode can be enabled and run. If the OAT rises

above this threshold during heating, then heating will not

be allowed.

Factory Default = 65_F

Range = 49--95_F

548J