Fig. 52 -- RTU--MP T--55 Sensor Connections

Connect T--56 -- See Fig. 53 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to

RTU--MP J20--1, J20--2 and J20--3 per Fig. 54.

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C08202

Fig. 53 -- T--56 Internal Connections

SEN

J20-1

J20-2

SEN

SET

Jumper

J20-3

SET

C08461

Fig. 54 -- RTU--MP T--56 Sensor Connections

Connect T--59 -- The T--59 space sensor requires a

separate, isolated power supply of 24 VAC. See Fig. 55

for internal connections at the T--59. Connect the SEN

terminal (BLU) to RTU--MP J20--1. Connect the COM

terminal (BRN) to J20--2. Connect the SET terminal (STO

or BLK) to J20--3.

OR

SET

SEN

OPB

COM- PWR+

BLU (SPT)

BLK (STO)

24 VAC

SENSOR

WIRING

POWER
WIRING

BRN (COM)

NOTE: Must use a separate isolated transformer.

C07132

Fig. 55 -- Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Economizer controls —

Outdoor Air Enthalpy Control (PNO 33CSENTHSW) --

The enthalpy control (33CSENTHSW) is available as a

field--installed accessory to be used with the EconoMi$er2

damper system. The outdoor air enthalpy sensor is part of

the enthalpy control. (The separate field--installed

accessory return air enthalpy sensor (33CSENTSEN) is

required for differential enthalpy control. See “Return Air

Enthalpy Sensor” for details.)

Locate the enthalpy control in the economizer next to the

Actuator Motor. Locate two GRA leads in the factory

harness and connect the gray lead labeled “ESL” to the

terminal labeled “LOW”. See Fig. 56. Connect the

enthalpy control power input terminals to economizer

actuator power leads RED (connect to 24V) and BLK

(connect to GND).

7

ESL

CTB
ECON

LOW

GND

24V

Enthalpy
Switch

GRA

BLK

RED

Factory Wiring Harness

ECONO
MOTOR

C09026

Fig. 56 -- Enthalpy Switch (33CSENTHSW) Connections

The outdoor enthalpy changeover setpoint is set at the

enthalpy controller.

The enthalpy control receives the outdoor air enthalpy

from the outdoor air enthalpy sensor and provides a dry

contact switch input to the RTU--MP controller. A closed

contact indicates that outside air is preferred to the return

air. An open contact indicates that the economizer should

remain at minimum position.