Warning, Convenience outlets – Bryant 548J User Manual

Page 19

Advertising
background image

19

CONVENIENCE OUTLETS

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Units with convenience outlet circuits may use

multiple disconnects. Check convenience outlet for

power status before opening unit for service. Locate

its disconnect switch, if appropriate, and open it.

Tag--out this switch, if necessary.

!

WARNING

Two types of convenience outlets are offered on 548J

models: Non--powered and unit--powered. Both types

provide a 125--volt GFCI (ground--fault circuit--interrupter)

duplex receptacle rated at 15--A behind a hinged waterproof

access cover, located on the end panel of the unit. See

Fig. 22.

Convenience

Outlet

GFCI

Pwd-CO

Fuse

Switch

Pwd-CO

Transformer

Control Box

Access Panel

C08128

Fig. 22 -- Convenience Outlet Location

Installing Weatherproof Cover –

A

weatherproof

while-in-use

cover

for

the

factory-installed convenience outlets is now required by

UL standards. This cover cannot be factory-mounted due

its depth; it must be installed at unit installation. For

shipment, the convenience outlet is covered with a blank

cover plate.

The weatherproof cover kit is shipped in the unit’s control

box. The kit includes the hinged cover, a backing plate

and gasket.

DISCONNECT

ALL

POWER

TO

UNIT

AND

CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet;

discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until

approximately

1

/

2

-in (13 mm) under screw heads are

exposed. Press the gasket over the screw heads. Slip the

backing plate over the screw heads at the keyhole slots

and align with the gasket; tighten the two screws until

snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as

shown in Fig. 23. Remove two slot fillers in the bottom of

the cover to permit service tool cords to exit the cover.

Check for full closing and latching.

RECEPTACLE
NOT INCLUDED

COVER – WHILE-IN-USE
WEATHERPROOF

BASE PLATE FOR
GFCI RECEPTACLE

C09022

Fig. 23 -- Weatherproof Cover Installation

Non--powered type: This type requires the field

installation of a general--purpose 125--volt 15--A circuit

powered from a source elsewhere in the building. Observe

national and local codes when selecting wire size, fuse or

breaker requirements and disconnect switch size and

location. Route 125--v power supply conductors into the

bottom of the utility box containing the duplex receptacle.

Unit--powered type: A unit--mounted transformer is

factory--installed to stepdown the main power supply

voltage to the unit to 115--v at the duplex receptacle. This

option also includes a manual switch with fuse, located in

a utility box and mounted on a bracket behind the

convenience outlet; access is through the unit’s control

box access panel. See Fig. 22.

The primary leads to the convenience outlet transformer

are not factory--connected. Selection of primary power

source is a customer--option. If local codes permit, the

transformer primary leads can be connected at the

line--side terminals on the unit--mounted non--fused

disconnect or HACR breaker switch; this will provide

service power to the unit when the unit disconnect switch

or HACR switch is open. Other connection methods will

result in the convenience outlet circuit being de--energized

when the unit disconnect or HACR switch is open. See

Fig. 24.

Duty Cycle: the unit--powered convenience outlet has a

duty cycle limitation. The transformer is intended to

provide power on an intermittent basis for service tools,

lamps, etc; it is not intended to provide 15--amps loading

for continuous duty loads (such as electric heaters for

overnight use). Observe a 50% limit on circuit loading

above 8--amps (i.e., limit loads exceeding 8--amps to 30

minutes of operation every hour).

Test the GFCI receptacle by pressing the TEST button on

the face of the receptacle to trip and open the receptacle.

Check for proper grounding wires and power line phasing

548J