Warning – Bryant 548J User Manual

Page 4

Advertising
background image

4

Outside Air Hood
Outside

air

hood

inlet

screens

are

permanent

aluminum--mesh type filters. Check these for cleanliness.

Remove the screens when cleaning is required. Clean by

washing with hot low--pressure water and soft detergent

and replace all screens before restarting the unit. Observe

the flow direction arrows on the side of each filter frame.

Economizer Inlet Air Screen

This air screen is retained by spring clips under the top

edge of the hood. (See Fig. 3.)

DIVIDER

BAROMETRIC

RELIEF

CLEANABLE

ALUMINUM

FILTER

FILTER

HOOD

FILTER

CLIP

OUTSIDE

AIR

C08634

Fig. 3 -- Filter Installation

To remove the filter, open the spring clips. Re--install the

filter by placing the frame in its track, then closing the

spring clips.

Manual Outside Air Hood Screen

This inlet screen is secured by a retainer angle across the

top edge of the hood. (See Fig. 4.)

C07156

Fig. 4 -- Screens Installed on Outdoor--Air Hood

(Sizes 08D--09D Shown)

To remove the screen, loosen the screws in the top retainer

and slip the retainer up until the filter can be removed.

Re--install by placing the frame in its track, rotating the

retainer back down and tighten all screws.

SUPPLY FAN (BLOWER) SECTION

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal

injury or death.
Before performing service or maintenance operations

on the fan system, shut off all unit power and tag--out

the unit disconnect switch. Do not reach into the fan

section with power still applied to unit.

!

WARNING

Supply Fan (Direct--Drive)

For unit sizes 04, 05 and 06, the Standard Static supply

fan system consists of a direct--drive forward--curved

centrifugal blower wheel attached to the motor shaft. The

motor has taps to provide the servicer with the selection of

one of five motor torque/speed ranges to best match wheel

performance with attached duct system. See Fig. 5 (548J

Direct--Drive Fan Assembly) and Fig. 6 (EMC Motor

Connectors).

EMC Motor

Motor Plug Position

(95° from vertical)

95°

EMC Power
Transformer
(460, 575v)

C09260

Fig. 5 -- 548J Direct--Drive Supply Fan Assembly

L2

YEL

Gnd

GRN/YEL

L1

BLU

C

1 2 3 4 5

L G N

Motor

Power

Connections

Speed

Taps

Com
BRN

VIO
Default Connection

C09261

Fig. 6 -- EMC Motor Connectors

548J