6. For units with an economizer, the sampling tube is in-

tegrated into the economizer housing but the connec-

tion of the flexible tubing to the sampling tube is the

same.

C08127

Fig. 41 -- Return Air Sensor Operating Position

FIOP Smoke Detector Wiring and Response

All units: FIOP smoke detector is configured to

automatically shut down all unit operations when smoke

condition is detected. See Fig. 42, Typical Smoke

Detector System Wiring.

Highlight A: JMP 3 is factory--cut, transferring unit

control to smoke detector.

Highlight B: Smoke detector NC contact set will open on

smoke alarm condition, de--energizing the ORN

conductor.

Highlight C: 24--v power signal via ORN lead is removed

at Smoke Detector input on CTB (Control Terminal

Board); all unit operations cease immediately.

Highlight D: On smoke alarm condition, the smoke

detector NO Alarm contact will close, supplying 24--v

power to GRA conductor.

Highlight E: GRA lead at Smoke Alarm input on CTB

provides 24--v signal to FIOP DDC control.

RTU--MP: The 24--v signal is conveyed to RTU--MP’s

J1--10 input terminal. This signal initiates the FSD

sequence by the RTU--MP control. FSD status is reported

to connected BAS network.

Using Remote Logic: Five conductors are provided for

field use (see Highlight F in Fig. 42) for additional

annunciation functions.

Additional Application Data — Refer to Catalog No.

HKRNKA--1XA for discussions on additional control

features of these smoke detectors including multiple unit

coordination. See Fig. 42.

A

E

F

C

D

B

C08246

Fig. 42 -- Typical Smoke Detector System Wiring

548J