Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus

weatherproof enclosure) — The outdoor air CO

2

sensor is

designed to monitor carbon dioxide (CO

2

) levels in the

outside ventilation air and interface with the ventilation

damper in an HVAC system. The OAQ sensor is packaged

with an outdoor cover. See Fig. 60. The outdoor air CO

2

sensor must be located in the economizer outside air hood.

COVER REMOVED

SIDE VIEW

C07135

Fig. 60 -- Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO

2

Sensor — A dedicated power

supply is required for this sensor. A two--wire cable is

required to wire the dedicated power supply for the sensor.

The two wires should be connected to the power supply

and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 58. Connect the 4--20 mA terminal

to RTU--MP J4--5. Connect the SIG COM terminal to

RTU--MP J4--6. See Fig. 61.

SEN

COM

J4-5

J4-6

OAQ Sensor/RH Sensor

24 VAC

C08463

Fig. 61 -- RTU--MP / Outdoor CO

2

Sensor

(33ZCSENCO2) Connections

On 548J units equipped with factory--installed Smoke

Detector(s), the smoke detector controller implements the

unit shutdown through its NC contact set connected to the

unit’s CTB input. The FSD function is initiated via the

smoke detector’s Alarm NO contact set. The RTU--MP

controller communicates the smoke detector’s tripped

status to the BAS building control. See Fig. 42 for unit

smoke detector wiring.

The

Fire

Shutdown

Switch

configuration,

MENU

Config

Inputs

input

5,

identifies

the

normally open status of this input when there is no fire

alarm.

Alarm state is reset when the smoke detector alarm

condition is cleared and reset at the smoke detector in the

unit.

Connecting Discrete Inputs

Filter Status
The filter status accessory is a field--installed accessory.

This accessory detects plugged filters. When installing

this accessory, the unit must be configured for filter status

by setting MENU

Config

Inputs

input 3, 5, 8, or 9

to Filter Status and normally open (N/O) or normally

closed (N/C). Input 8 or 9 is recommended for easy of

installation. Refer to Fig. 46, Fig. 47 and Fig. 48 for wire

terminations at J5.
Fan Status
The fan status accessory is a field--installed accessory.

This accessory detects when the indoor fan is blowing air.

When installing this accessory, the unit must be

configured

for

fan

status

by

setting

MENU

Config

Inputs

input 3, 5, 8, or 9 to Fan

Status and normally open (N/O) or normally closed (N/C).

Input 8 or 9 is recommended for easy of installation. Refer

to Fig. 46, Fig. 47, and Fig. 48 for wire terminations at J5.
Remote Occupancy
The remote occupancy accessory is a field--installed

accessory. This accessory overrides the unoccupied mode

and puts the unit in occupied mode. When installing this

accessory, the unit must be configured for remote

occupancy by setting MENU

Config

Inputs

input 3,

5, 8, or 9 to Remote Occupancy and normally open (N/O)

or normally closed (N/C).
Also set MENU

Schedules

occupancy source to DI

on/off. Input 8 or 9 is recommended for easy of

installation. Refer to Fig. 46 and Table 14 for wire

terminations at J5.

Power Exhaust (output)

Connect the accessory Power Exhaust contactor coil(s) per

Fig. 62.

Power Exhaust

J11-3

C

TAN

GRA

PEC

CTB

THERMOSTAT

C08464

Fig. 62 -- RTU--MP Power Exhaust Connections

Space Relative Humidity Sensor -- The RH sensor is not

used with 548J models at this time.

Communication Wiring -- Protocols

General
Protocols are the communication languages spoken by

control devices. The main purpose of a protocol is to

communicate information in the most efficient method

possible. Different protocols exist to provide different

kinds of information for different applications. In the BAS

application, many different protocols are used, depending