Internal Wiring

Check all electrical connections in unit control boxes.

Tighten as required.

Refrigerant Service Ports

Each unit system has two

1

/

4

” SAE flare (with check

valves) service ports: one on the suction line, and one on

the compressor discharge line. Be sure that caps on the

ports are tight.

Compressor Rotation

On 3--phase units with scroll compressors, it is important

to be certain compressor is rotating in the proper

direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect service gauges to suction and discharge

pressure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start--up.

If the suction pressure does not drop and the discharge

pressure does not rise to normal levels:

1. Note that the evaporator fan is probably also rotating

in the wrong direction.

2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Re--energize to the compressor. Check pressures.

The suction and discharge pressure levels should now

move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong

direction, the unit will make an elevated level of noise
and will not provide cooling.

Cooling

Set space thermostat to OFF position. To start unit, turn on

main power supply. Set system selector switch at COOL

position and fan switch at AUTO. position. Adjust

thermostat to a setting below room temperature.

Compressor starts on closure of contactor. (08D–09D:

Second stage of thermostat will energize Circuit 2

contactor, start Compressor 2.)

Check unit charge. Refer to Refrigerant Charge section.

Reset thermostat at a position above room temperature.

Compressor will shut off. Evaporator fan will shut off

after a 30--second delay.

To shut off unit -- set system selector switch at OFF

position. Resetting thermostat at a position above room

temperature shuts unit off temporarily until space

temperature exceeds thermostat setting.

Heating

To start unit, turn on main power supply.

Set system selector switch at HEAT position and set

thermostat at a setting above room temperature. Set fan at

AUTO position.

First stage of thermostat energizes compressor heating

(08D–09D: both compressors will start). Second stage of

thermostat energizes electric heaters (if installed). Check

heating effects at air supply grille(s).

If electric heaters do not energize, reset limit switch

(located on supply--fan scroll) by pressing button located

between terminals on the switch.

To shut off unit -- set system selector switch at OFF

position. Resetting thermostat at a position below room

temperature temporarily shuts unit off until space

temperature falls below thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF

positions, respectively. Supply fan operates continuously

to provide constant air circulation.

START--UP, RTU--MP CONTROL

Field Service Test, explained below, will assist in proper

start--up. Configuration of unit parameters, scheduling

options, and operation are also discussed in this section.

Field Service Test

The Field Service Test function can be used to verify

proper operation of compressors, heating stages, indoor

fan,

power

exhaust

fans,

economizer,

and

dehumidification. Use of Field Service Test is

recommended at initial system start up and during

troubleshooting.
Field Service Test mode has the following changes from

normal operation:

S

Outdoor air temperature limits for cooling circuits,

economizer, and heating are ignored.

S

Normal compressor time guards and other staging delays

are ignored.

S

The status of Alarms (except Fire and Safety chain) is

ignored but all alerts and alarms are still broadcasted on

the network.

Field Service Test can be turned ON/OFF at the unit

display or from the network. Once turned ON, other

entries may be made with the display or through the

network. To turn Field Service Test on, change the value

of Test Mode to ON, to turn Field Service Test off, change

the value of Test Mode to OFF.
NOTE: Service Test mode is password protected when

accessing from the display. Depending on the unit model,
factory--installed options, and field--installed accessories,
some of the Field Service Test functions may not apply.
The independent outputs (IndpOutputs) submenu is used

to change output status for the supply fan, economizer,

and Power Exhaust. These independent outputs can

operate simultaneously with other Field Service Test

modes. All outputs return to normal operation when Field

Service Test is turned off.
The Cooling submenu is used to change output status for

the individual compressors and the dehumidification relay.

Compressor starts are not staggered. The fans and heating

service test outputs are reset to OFF for the cooling

548J