9 calibration – B&B Electronics Network Device I-7011 User Manual

Page 15

Advertising
background image

15

I-7011, I-7018 User Manual

Rev:B1.0

1.9 Calibration

Don’t Perform Calibrate Until You Really Understand.

Calibration Requirement for I-7011/11D/11P/11PD/18/18P

Notification :

1

While calibrate type 06, need connect external shunt resistor,

125 ohms, 0.1% (Ref Sec.1.5).

2

Connect calibration voltage(or current) signal to module’s

input. For I-7018/18P, connect to channel 0. (Wire connect ref

Sec.1.5)

3

Before calibration, warm-up module about 30 minutes for bet-

ter accuracy.

Example Calibration Sequence for Type 00 :

1

Setting Type to 00

->

Ref

Sec.2.1.

2

Enable Calibration

->

Ref

Sec.2.20.

3

Apply Zero Calibration Voltage (0mV)

4

Preform Zero Calibration Command

-> Ref Sec.2.6.

5

Apply Span Calibration Voltage (15mV)

6

Perform Span Calibration Command

-> Ref Sec.2.5.

7

Repeat step1 to step6 three times.

Calibration sequence for other type is similiar but different in step

1 to set different type.

Type Code

00

01

02

03

04

05

06

Min. Input

0 mV

0 mV

0 mV

0 mV

0 V

0 V

0 mA

Max Input

+15

mV

+50

mV

+100

mV

+500

mV

+1 V

+2.5 V

+20

mA