18 $aaz(data), 17 $aam 2.18 $aaz(data) – B&B Electronics Network Device I-7011 User Manual

Page 39

Advertising
background image

39

I-7011, I-7018 User Manual

Rev:B1.0

2.18 $AAZ(Data)

Description : Set LED Data

Syntax : $AAZ(Data)[CHK](cr)

$

delimiter character

AA

address of setting module (00 to FF)

Z

command for setting LED data

(Data)

data for show on the LED, from -19999. to +19999. The

data need sign, 5 digits and decimal point.

Response :

Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command or LED not set to host

control

AA

address of response module (00 to FF)

Example :

Command : $01Z+123.45

Receive : !01

Send address 01 LED data +123.45, return success.

Command : $02Z+512.34

Receive : ?02

Send address 02 LED data +512.34, return the LED is not

setting in the host mode.

Related Command :

Sec.2.12 $AA8, Sec2.13 $AA8V

Note : The command is for I-7011D/11PD only