23 @aaeat, 22 @aado(data) 2.23 @aaeat – B&B Electronics Network Device I-7011 User Manual

Page 45

Advertising
background image

45

I-7011, I-7018 User Manual

Rev:B1.0

2.23 @AAEAT

Description : Enable Alarm

Syntax : @AAEAT[CHK](cr)

@

delimiter character

AA

address of setting module (00 to FF)

EA

command for enable alarm.

T

alarm type, M=momentary alarm, L=latch alarm.

Response :

Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example :

Command : @01EAM

Receive : ?01

Set address 01 momentary alarm, return success.

Related Command :

Sec.2.26 @AADA, Sec.2.27 @AACA

Related Topic :

Sec.3.6 High/Low Alarm

Note : The command is for I-7011/11D/11P/11PD only