23 @aaeat, 22 @aado(data) 2.23 @aaeat – B&B Electronics Network Device I-7011 User Manual
Page 45
Advertising
![background image](/manuals/53852/45/background.png)
45
I-7011, I-7018 User Manual
Rev:B1.0
2.23 @AAEAT
Description : Enable Alarm
Syntax : @AAEAT[CHK](cr)
@
delimiter character
AA
address of setting module (00 to FF)
EA
command for enable alarm.
T
alarm type, M=momentary alarm, L=latch alarm.
Response :
Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command
AA
address of response module(00 to FF)
Example :
Command : @01EAM
Receive : ?01
Set address 01 momentary alarm, return success.
Related Command :
Sec.2.26 @AADA, Sec.2.27 @AACA
Related Topic :
Sec.3.6 High/Low Alarm
Note : The command is for I-7011/11D/11P/11PD only