26 @aada – B&B Electronics Network Device I-7011 User Manual

Page 48

Advertising
background image

48

I-7011, I-7018 User Manual

Rev:B1.0

2.26 @AADA

Description : Disable Alarm

Syntax : @AADA[CHK](cr)

@

delimiter character

AA

address of setting module (00 to FF)

DA

command for disable alarm

Response :

Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example :

Command : @01DA

Receive : !01

Disable address 01 alarm, return success.

Related Command :

Sec.2.23 @AAEAT

Related Topic :

Sec.3.6 High/Low Alarm

Note : The command is for I-7011/11D/11P/11PD only