34 ~aa1 – B&B Electronics Network Device I-7011 User Manual

Page 56

Advertising
background image

56

I-7011, I-7018 User Manual

Rev:B1.0

2.34 ~AA1

Description : Reset Module Status

Syntax : ~AA1[CHK](cr)

~

delimiter character

AA

address of setting module (00 to FF)

1

command for reset module status

Response :

Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example :

Command : ~010

Receive : !0104

Read address 01 module status, return 04, host watchdog

timeout flag is set.

Command : ~011

Receive : !01

Reset address 01 module status, return success.

Command : ~010

Receive : !0100

Read address 01 module status, return 00, Module Status is

clear.

Related Command :

Sec.2.32 ~**, Sec.2.33 ~AA0

Related Topic :

Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation