3 #aa – B&B Electronics Network Device I-7011 User Manual
Page 24
24
I-7011, I-7018 User Manual
Rev:B1.0
2.3 #AA
Description : Read Analog Input
Syntax : #AA[CHK](cr)
#
delimiter character
AA
address of reading module(00 to FF)
Response :
Valid Command :
>(Data)[CHK](cr)
Syntax error or communication error may get no re-
sponse.
>
delimiter for valid command
(Data)
analog input value, reference Sec.1.10 for its format.
For I-7018/18P, the data is the combination for each chan-
nel respectively.
Example :
Command : #01
Receive : >+02.635
Read address 01, return data success.
Command : #02
Receive : >4C53
Read address 02, return data in HEX format success.
Command : #04
Receive : >+05.123+04.153+07.234-02.356+10.000-
05.133+02.345+08.234
Module address 04 is I-7018. Read address 04, get analog input
data of 8 channels.
Related Command :
Sec.2.1 %AANNTTCCFF, Sec.2.7 $AA2
Related Topics :
Sec.1.10 Configuration Tables