10 configuration tables, Analog input type and data format table – B&B Electronics Network Device I-7011 User Manual

Page 17

Advertising
background image

17

I-7011, I-7018 User Manual

Rev:B1.0

Type

Code

Input Range

Data Format

+F.S.

Zero

-F.S.

00

-15 to +15

mV

Engineer Unit

+15.000 +00.000 -15.000

% of FSR

+100.00 +000.00 -100.00

2's complement HEX

7FFF

0000

8000

01

-50 to +50

mV

Engineer Unit

+50.000 +00.000 -50.000

% of FSR

+100.00 +000.00 -100.00

2's complement HEX

7FFF

0000

8000

02

-100 to +100

mV

Engineer Unit

+100.00 +000.00 -100.00

% of FSR

+100.00 +000.00 -100.00

2's complement HEX

7FFF

0000

8000

03

-500 to +500

mV

Engineer Unit

+500.00 +000.00 -500.00

% of FSR

+100.00 +000.00 -100.00

2's complement HEX

7FFF

0000

8000

04

-1 to +1 V

Engineer Unit

+1.0000 +0.0000 -1.0000

% of FSR

+100 00 +000 00 -100 00

Analog input type and data format table