49

I-7011, I-7018 User Manual

Rev:B1.0

2.27 @AACA

Description : Clear Latch Alarm

Syntax : @AACA[CHK](cr)

@

delimiter character

AA

address of setting module (00 to FF)

CA

command for clear latch alarm

Response :

Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example :

Command : @01DI

Receive : !0120101

Read address 01 digital input, return latch alarm mode, low

alarm is set.

Command : @01CA

Receive : !01

Clear address 01 latch alarm, return success.

Command : @01DI

Receive : !0120001

Read address 01 digital input, return latch alarm mode, both

alarms are clear.

Related Command :

Sec.2.21 @AADI, Sec.2.23 @AAEAT, Sec.2.26 @AADA

Related Topic :

Sec.3.6 High/Low Alarm

Note : The command is for I-7011/11D/11P/11PD only