38 ~aa5ppss – B&B Electronics Network Device I-7011 User Manual

Page 60

Advertising
background image

60

I-7011, I-7018 User Manual

Rev:B1.0

2.38 ~AA5PPSS

Description : Set PowerOn Value and Safe Value

Syntax : ~AA5PPSS[CHK](cr)

~

delimiter character

AA

address of setting module (00 to FF)

5

command for setting PowerOn Value and Safe Value

PP

PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on, DO1

off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on

SS

Safe Value, data format is same as PP

Response :

Valid Command :

!AA[CHK](cr)

Invalid Command :

?AA[CHK](cr)

Syntax error or communication error may get no re-

sponse.

!

delimiter for valid command

?

delimiter for invalid command

AA

address of response module(00 to FF)

Example :

Command : ~0150003

Receive : !01

Set address 01 PowerOn Value is DO0 off, DO1 off, Safe Value

is DO0 on, DO1 on, return success.

Related Command :

Sec.2.37 ~AA4

Related Topic :

Sec.3.2 Module Status, Sec.3.3 Dual Watchdog Operation

Note : The command is for I-7011/11D/11P/11PD only

Advertising