5 $aa0 – B&B Electronics Network Device I-7011 User Manual
Page 26
26
I-7011, I-7018 User Manual
Rev:B1.0
2.5 $AA0
Description : Perform Span Calibration
Syntax : $AA0[CHK](cr)
$
delimiter character
AA
address of setting module (00 to FF)
0
command for performing span calibration
Response :
Valid Command :
!AA[CHK](cr)
Invalid Command :
?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
!
delimiter for valid command
?
delimiter for invalid command or the calibration is not
enabled
AA
address of response module(00 to FF)
Example :
Command : $010
Receive : !01
Perform address 01 span calibration, return success.
Command : $020
Receive : ?02
Perform address 02 span calibration, return the calibration is
not enabled before perform calibration command.
Related Command :
Sec.2.6 $AA1, Sec.2.20 ~AAEV
Related Topics :
Sec.1.9 Calibration