Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide

377

53-1002373-02

Replacing fan assemblies

8

6. Place the handle over the upward deflector aligning the handle with the screw holes and

secure the handle to the upward deflector and fan assembly faceplate with the two screws.
Refer to

Figure 251

.

FIGURE 251

Upward deflector oriented correctly between the handle and fan assembly faceplate

7. Re-attach the fan assembly faceplate to the fan assembly by securing three screws on each

side.

NOTE

Replacing the tape is not required.

Reinstalling the modified fan assembly in the chassis

To reinstall the modified fan assembly, complete the following steps:

1. Insert the modified fan assembly into the fan slot and push the assembly in until the fan

assembly faceplate is flush with the chassis. Pushing the fan assembly in seats the fan
connector in the router connector.

2. Secure the fan assembly to the router by replacing and tightening the four screws.

3. Check the fan status LED in the lower left corner of the faceplate. It will glow red momentarily

when power is applied, and then it will change to green when the fan comes up to speed.

4. To verify that the fan is operating correctly, access the CLI and enter the show chassis

command.